Powerware UPS 1000 - 2200 User Manual
Page 18
1000 - 2000 VA
User’s Manual
1019297
Revision A
18
Use the following procedure to replace internal batteries:
1.
Remove the UPS front panel by pulling the top.
2.
Slide up and remove the metal battery cover.
3.
1000 VA units. Disconnect the red battery cable on the front of the battery. Pull the
battery out onto a flat, stable surface. Disconnect the black battery cable on the rear
of the battery, then on the front of the battery. Disconnect the red battery cable on
the rear of the battery. See “Recycling the Used Battery” on page 20 for proper
disposal.