Local Configuration
9
BestLink SNMP/WEB Adapter User’s Guide
:
LTM-1343 B Draft 10/03/2001
4. Turn on the UPS.
After a few seconds the PC displays a message indicating that the
adapter is ready.
5. Press [Enter]. The Password screen appears (see Figure 6).
If the Password screen does not appear, press [Enter] again.
If you still do not see the Password screen, check the following
conditions:
: The communication settings of the terminal should be 9600 baud,
No parity, 8 bits, and 1 stop bit.
: If the serial configuration is correct, check the cabling to verify all
connections are secure.
: Verify that your terminal program is on the correct
communication port for the serial connection.
: Verify that the UPS has input power and is turned on.
6. Type your password (the default password is admin) and press
[Enter]. The Main Menu screen appears.
+============================================================================+
|
[ BestLink SNMP/WEB Adapter Configuration Utility ]
|
+============================================================================+
Enter Password: *****
+============================================================================+
|
[ BestLink SNMP/WEB Adapter Configuration Utility ]
|
+============================================================================+
1. SNMP/WEB Card Settings
2. Reset Configuration to default
3. Restart SNMP/WEB Card
0. Exit
Please Enter Your Choice =>_
Figure 6. BestLink SNMP/WEB Adapter Main Menu Screen