9−1

EATON Powerware

®

9315 UPS (200–300 kVA) Operation Manual

S 164201036 Rev G www.powerware.com

Chapter 9

Product Specifications

The UPS systems are housed in freestanding, double-front cabinets with safety shields
behind the doors. The UPS systems are available in 50/60 Hz with various output power
ratings. Smaller models within a system may be upgraded in the field to larger models:

Table 9-1. Model Numbers

System

Models

Notes

Powerware 9315 300

225 and 300 kVA

60 Hz only

Powerware 9315 250

200 and 250 kVA

50/60 Hz (400V models only)

Powerware 9315 225

225 kVA

60 Hz only

Powerware 9315 200

200 kVA

50/60 Hz (400V models only)

The following sections detail the input, output, environmental, and battery specifications
for the UPS.

Table 9-2. System Input

Operating Input
Voltage
(Nominal +10/–15%)

480 Vac for operation from 408 Vac to 528 Vac (60 Hz only)
400 Vac for operation from 340 Vac to 440 Vac (50/60 Hz only)
600 Vac for operation from 510 Vac to 660 Vac (60 Hz only)

Operating Input
Frequency Range

"3 Hz of nominal (50 Hz or 60 Hz)

Operating Input
Current

Battery Charge

125% of full load for overload + battery charge

Actual load + 25% of full load for battery charge with 0.8 pF
output units

115% of full load for overload + battery charge

Actual load + 15% of full load for battery charge with 0.9 pF
output units

Reduced for Generator

Adjustable, set to 102%

Input Current
Harmonic Content

10% THD at full load (with input filter option installed)

Power Walk-In

Adjustable 3–60 second rectifier ramp-up to full utility load

Power Factor

Minimum 0.95

Line Surges

6 kV OC, 3 kA SC per ANSI 62.41 and IEC 801-4