beautypg.com

Figure 7-3. port 1 (db−9) pin assignments, Figure 7-4. port 2 (db−25) pin assignments, Pin assignments for port 1 (db-9) – Powerware 9315 UPS User Manual

Page 50

background image

Communication

7−4

EATON Powerware

®

9315 UPS (200–300 kVA) Operation Manual

S 164201036 Rev G www.powerware.com

NOT USED

485–

485+

RETURN

7

8

9

1

5

4

3

2

+24V

RS-232 TXD

RS-232 RXD

NOT USED

RETURN

6

Figure 7-3. Port 1 (DB−9) Pin Assignments

Table 7-1.

Pin Assignments for Port 1 (DB-9)

Pin Number

Symbol

Function

Comments

1

+24V

+24 Volts DC

2

TXD

Transmit Data

Input to UPS

3

RXD

Receive Data

Output from UPS

5

RTN

Return

7

485+

RS-485 + Data

8

485–

RS-485 – Data

9

RTN

Return

NOTE

The X−Slot communication bay is connected internally to the DB−25 port by

default; the DB−25 is disabled for other uses. Contact your Eaton service representative
to purchase, install, and set up an external modem or an internal X−Slot Modem Card.

NOT USED

NOT USED

NOT USED

NOT USED

NOT USED

NOT USED

RS-232 DTR

NOT USED

–12V

NOT USED

NOT USED

NOT USED

23

21

19

17

15

12

1

5

4

3

2

GND

RS-232 TXD

RS-232 RXD

RS-232 RTS

RS-232 CTS

6

10

9

8

7

RS-232 DSR

RTN

+12V

NOT USED

NOT USED

11

13

NOT USED

NOT USED

NOT USED

24

22

25

20

18

16

14

Figure 7-4. Port 2 (DB−25) Pin Assignments