beautypg.com

Preinstallation – PB Heat MI/MIH series User Manual

Page 5

background image

3

where:
I

other

= Input of appliances other than fan

assisted in Btu/hr

ACH = air change per hour (percent of the

volume of the space exchanged per
hour, expressed as a decimal)

For fan assisted appliances, calculate the required
volume of air using the following equation:

I

fan

= Input of the fan assisted appliances in

Btu/hr

Note: These calculations are not to be used for
infiltration rates greater than 0.60 ACH.

3. Indoor Air Opening Size and Location: Openings

connecting indoor spaces shall be sized and located
as follows:

a. Combining spaces on the same floor:

Provide two permanent openings communicating
with additional spaces that have a minimum free
area of 1 in

2

per 1000 Btu/hr (22 cm

2

per 1000 W)

of the total input rating of all gas fired equipment
but not less than 100 in

2

(645 cm

2

). One

opening is to begin within 12 inches (305 mm)
from the top of the space and the other is to
begin within 12 inches (305 mm) from the floor.
The minimum dimension of either of these
openings shall be 3 inches (76 mm). See Figure
1.1 for an illustration of this arrangement.

b. Combining spaces on different floors:

Provide one or more permanent openings
communicating with additional spaces that have
a total minimum free area of 2 in

2

per 1000

Btu/hr (44 cm

2

per 1000 W) of total input rating

of all equipment. See Figure 1.2 for an
illustration of this arrangement.

4. Outdoor Combustion Air: Outdoor combustion air is

to be provided through one or two permanent
openings. The minimum dimension of these air
openings is 3 inches (76 mm).

a. Two Permanent Opening Method: Provide

two permanent openings. One opening is to
begin within 12 inches (305 mm) of the top of
the space and the other is to begin within 12
inches (305 mm) of the floor. The openings are
to communicate directly or by ducts with the
outdoors or with spaces that freely communicate
with the outdoors. The size of the openings shall
be determined as follows:

i.

Where communicating directly or through
vertical ducts with the outdoors each opening
shall have a minimum free area of 1 in

2

per

4000 Btu/hr (22 cm

2

per 4000 W) of total

input rating for all equipment in the space.
See Figure 1.3 for openings directly
communicating with the outdoors or Figure
1.4 for openings connected by ducts to the
outdoors.

PREINSTALLATION

15 ft

3

I

fan

ACH

1000

Btu

/

hr

Required Volume

fan

=

Figure 1.1:

Air Openings – All Air from Indoors
on the Same Floor

Figure 1.2:

Air Openings – All Air from Indoors
on Different Floors

Figure 1.3:

Air Openings – All Air Directly from
Outdoors