E. ANNUALLY (BEFORE START OF HEATING

SEASON)

1. Check flueways and burners for cleanliness and clean

if necessary. Use the following procedure if cleaning
is required:

a. Refer to the Lighting/Operating Instructions in

Figures 7.4 and 7.5 to properly turn off the gas to
the boiler.

b. Turn off all electrical power to the boiler.

c. Remove burners and brush orifice spuds lightly

using a soft bristle brush.

d. Remove the vent pipe, vent damper, top jacket

panels and flue collector/draft diverter. Remove
baffles on MIH models.

e. Brush flueways with wire brush.

f.

To the extent possible, inspect inside of vent pipe
and vent damper for obstructions in flow or vent
damper movement. Remove or replace as
necessary.

g. Re-install baffles on MIH models. When replacing

the flue collector/draft hood, be certain that the
blanket seal between the flue collector and top
section makes a tight seal to prevent leakage of
the products of combustion.

h. Re-install the top of the jacket, vent damper and

vent pipe.

i.

Re-install burners.

2. Inspect entire venting system for corrosion, support

and joint integrity. Repair as necessary.

3. Check the pilot and main burner flame. See Figures

9.1 and 9.2. The pilot should provide a steady flame
enveloping 3/8

″ to 1/2″ (1 cm to 1.2 cm) of the

flame sensor. If required, adjust the pilot as stated in
the gas valve manufacturer’s instructions or
paragraph 7.D. The main burner flame inner cone
should be approximately 1-1/2

″ (4 cm) high and

should have a very sharp, blue color characteristic.

MAINTENANCE

Figure 9.1: Standing Pilot and Main Burner Flame

Figure 9.2: Intermittent Pilot and Main

Burner Flame

When servicing or replacing components, be
absolutely certain that the following conditions are
met:

Water, gas and electricity are off.

The boiler is at room temperature.

There is no pressure in the boiler.

DANGER