22

FUSE REPLACEMENT PROCEDURES

CAUTION: Before changing the input fuse, turn off the UPS, and unplug the
supply lead from the AC input supply and from the UPS. Replace the fuse with
the same type and rating.

Insert flat blade
screwdriver into slot
and turn fuse holder
to remove / install

Fuse Holder

Input Fuse

Remove

Install

1. Remove the fuse holder by inserting a flat blade screwdriver into the slot and

turning to remove as indicated in the figure above.

2. Remove the input fuse.
3. Locate the spare input fuse that is included with the UPS.
4. Insert the spare fuse into the fuse holder, and reinstall assembly into the

UPS. Using the screwdriver, rotate clockwise until fuse holder locks into
position.

5. Reconnect the input power lead to the UPS, and the input power lead to the

input AC supply.

6. Restart the UPS. The UPS is ready for normal operation.
NOTE: For 1500 VA, 2000 VA, and 3000 VA units, reset circuit protector.

AUDIBLE ALARM CONDITIONS

CONDITION

ALARM

Battery mode

(utility failure)

One short beep every ten seconds; more
than two minutes of run time remaining

Low battery

Two short beeps every five seconds; less
than two minutes of run time remaining

Output overload (bypass)

One short beep every half second

Over temperature (bypass)

One second beep every four seconds

DC Bus overvoltage (bypass)

One second beep every four seconds

Control power supply failure (bypass)

One second beep every four seconds

PFC failure (bypass)

One second beep every four seconds

Inverter failure

One second beep every four seconds

Battery Test failure

Two second beep every minute