Maintenance, Maintenance schedule – Lochinvar SQUIRE SIT030 User Manual
Page 18

18
Installation & Operation Manual
7
Maintenance
*
Make sure that the rest of the boiler and domestic 
water piping is free of leaks.
*
If there is an oil lubricated circulator in the system, 
make sure it is lubricated as called for by the 
circulator manufacturer.
*
Make sure that the boiler is maintained in accordance 
with the boiler manufacturer’s instructions.
*
If a water treatment system is required to keep the 
water chemistry within the parameters shown in 
Table 2A (see Section 2 - Pre-Installation), make sure 
that this system is properly maintained.
The Lochinvar SIT series indirect water heater is an extremely
simple device and as such requires very little maintenance.
There are, however, several items which should be checked
out on an annual or as needed basis to ensure a reliable supply
of hot water:
Maintenance Schedule
Annual service by a qualified service technician
should include the following:
Any procedure required by local codes.
Verify system pressure. Air venting procedure may 
require adding water to bring boiler system up to 
pressure, typically 12 psig.
Manually operate T&P relief valve at least once a year. 
This will release some hot water.
ƽ WARNING
Before operating a T&P relief valve, make
sure no one is in front of or around the
T&P relief valve discharge piping. Hot
discharge water can cause severe personal
injury or substantial property damage.
Move operating lever to open position for a few 
seconds and then move it back, allowing it to snap 
closed. After the T&P relief valve is operated, if it 
continues to release water, close the cold water inlet to 
the water heater immediately. Follow the draining 
instructions, and replace the T&P relief valve. If the 
T&P relief valve weeps periodically, it may be due to 
thermal expansion. Do not plug the T&P relief valve or 
discharge piping.
Review homeowner’s maintenance responsibilities and 
their frequencies, including any not listed in the 
following section.
Homeowner monthly maintenance to include:
Visually check valves, pipes, and fittings for leaks. Call a 
qualified service technician to repair leaks.
To Fill the Water Heater
1.
Close the water heater drain valve by turning the knob 
clockwise.
2.
Open the cold water supply shutoff valve.
3.
Open several hot water faucets to allow air to escape from 
the system.
4.
When a steady stream of water flows from the faucets, the 
water heater is filled. Close the faucets and check for water 
leaks at the water heater drain valve, combination 
temperature and pressure relief valve and the hot and cold 
water connections.
ƽ DANGER
Plugging the T&P relief valve or discharge
piping can cause excessive pressure in the
water heater, resulting in severe personal
injury, death, or substantial property
damage.
ƽ WARNING
Water from opened drain valves, unions and
other connections may be extremely hot. To
avoid severe personal injury, death, or
substantial property damage:
-
Tighten all drain hose connections.
-
Direct hot water away from all 
persons.
To Drain the Water Heater
Should it become necessary to completely drain the water
heater, be sure to follow the steps below:
1.
Disconnect the power supply to the heat source. C o n s u l t 
the plumbing professional or electric company in your area 
for service.
2.
Close the cold water supply shutoff valve.
3.
Open the drain valve on the water heater.
4.
Open a hot water faucet to allow air to enter the system.
•
If boiler water does not contain sufficient 
antifreeze, the boiler water and the domestic water 
must be drained.
If antifreeze is used in the boiler water, check concentration.
Boiler water (including additives) must be practically non-toxic,
having a toxicity rating or class of 1, as listed in the “Clinical
Toxicology of Commercial Products”. A maximum 50/50
mixture of inhibited propylene glycol is recommended. Follow
the antifreeze manufacturer’s instructions.
ƽ WARNING
Do not use automotive, ethylene glycol or
petroleum-based antifreeze. Do not use any
undiluted antifreeze. This can cause severe
personal injury, death, or substantial
property damage.
Drain the water heater if it will be shut off and exposed to
freezing temperatures. Freezing water will expand and damage
the water heater.
•
If boiler water contains sufficient antifreeze, then 
only the domestic water needs to be drained.
Follow instructions on circulator to oil, if required.
Check mixing valve, valves, pipes, and fittings for leaks.
Check function of the field-installed controls and valves. 
See component manufacturer’s instructions.
