Ups serial communications menu – Lucent Technologies Uninterruptible Power Systems 3000 VA User Manual
Page 57

Communication 5
Lucent Technologies Model 3000 UPS Operator's Manual (167Ć405Ć119 Issue 3)
47
3 Press and hold the Output
Off button a second timeuntil thealarm
beeps again.
A single indicator, corresponding with the current setting, remains
flashing.
4 Press the Output
Off button to scroll through thecommunication
options, top to bottom. Each timeyou press thebutton, theUPS beeps and
the next indicator flashes.
NOTE
If you do not save a selection within two minutes, the setup automatically aborts
and switches back to the original configuration.
5 Press and hold the Output
On button until the alarm beeps to select and
savea communication option. Failureto releasethebutton immediately
after thebeep will causetheUPS to abort thesetup.
6 Press the Output
On button again to return the UPS to Normal Mode.
NOTE
Printer Mode selections are the only serial communication modes available from
the front panel.
UPS Serial Communications Menu
With the UPS Serial Communications (Main) Menu, you can view or select UPS
communication modes, baud rates, and LAN configurations. To change or display
thecurrent communications configuration:
1 Connect the UPS serial port to a video monitor with a serial interface or to
your computer's serial port. If you are using shutdown software, the UPS
should already be connected to your computer.
2 Set your terminal so that it matches the baud rate of the UPS (usually
2400 baud, 8 bits, No parity, 1 stop bit). Refer to your terminal or
operating system documentation for details on configuring your terminal
communication settings.
3 At the terminal prompt, press
Control-C
until theUPS Serial
Communications Menu appears.
i
i