Repo installation – Lucent Technologies Uninterruptible Power Systems 3000 VA User Manual
Page 41

Installation 3
Lucent Technologies Model 3000 UPS Operator's Manual (167Ć405Ć119 Issue 3)
31
22 See the following table for specifications andtightening torque.
Power Cable Terminations
Tightening Torque
Wire Function
Terminal
Position
Terminal Wire
Size Rating*
Entrelec
Phoenix
Contact
Input
Ground
1
22-12 AWG
(0.34-4 mm
2
)
3.5 - 5.3 lb/in
5.6 - 6.8 lb/in
L1
2
lb/
lb/
L2/Neutral
3
18-10 AWG
2
3 5 5 3 lb/in
4 5 7 0 lb/in
Output
L1
5
(0.75-6 mm
2
)
3.5 - 5.3 lb/in
4.5 - 7.0 lb/in
L2/Neutral
6
Ground
8
22-12 AWG
2
3 5 5 3 lb/in
5 6 6 8 lb/in
No Connection
4, 7
(0.34-4 mm
2
)
3.5 - 5.3 lb/in
5.6 - 6.8 lb/in
*Use #16ĆAWG (1.5 mm
2
) 75_C copper wire minimum.
23 Replace the terminal box cover.
24 If you are using a Remote Emergency PowerĆOff (REPO) switch, follow the
instructions in REPO Installation" on page 31.
25 Start the UPS according to the UPS with Bypass Module Startup"
procedure on page 33.
REPO Installation
WARNING
Only qualified service personnel (such as a licensed electrician) should
perform the hardwired installation.
The REPO switch is a customerĆsuppliedswitch that can disconnect UPS output
voltage from your protectedequipment. To use a REPO switch, you needexternal
wiring anda switch with the following specifications:
H The switch shouldbe a wallĆmounted, momentaryĆcontact, normally open,
pushbutton switch.
H Minimum ratings of 240 Vac and35 mA.
H Wire shouldbe 18 AWG minimum.
CAUTION
The black and white REPO wires are at highĆvoltage potential (240V). Refer
to yourlocal electrical code forproperinstallation of the highĆvoltage REPO wires.