Table 3E (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Water Heater Interface

FAULT

DESCRIPTION

CORRECTIVE ACTION

Temp O/Shoot

(continued)

The temperature rise across the heat
exchanger has exceeded the set parameters
for the water heater.

• Verify that the system is full of water and that all air

has been properly purged from the system.

• Verify that the water heater is piped properly into the

heating system. Refer to Section 6 - System Piping
of the Armor Water Heater Installation and Operation
Manual for the proper piping methods for the Armor
water heater.

• Check for 120 VAC to the water heater pump motor on

a call for heat. If voltage is not present, check the
wiring back to the main control board. Replace the
main control board if necessary.

• If 120 VAC is present on a call for heat and the water

heater pump is not operating, replace the pump.

• Verify that the water heater pump is set to the proper

speed or that the pump is the proper size. Reference
Section 6 - System Piping of the Armor Water Heater
Installation and Operation Manual for water heater
pump specifications.

Outlet water temperature has exceeded the
maximum outlet water temperature.

• Verify that the system is full of water and that all air

has been properly purged from the system.

• Verify that the water heater is piped properly into the

heating system. Refer to Section 6 - System Piping
of the Armor Water Heater Installation and Operation
Manual for the proper piping methods for the Armor
water heater.

• Check for 120 VAC to the water heater pump motor on

a call for heat. If voltage is not present, check wiring
back to the main control board. Replace the main
control board if necessary.

• If 120 VAC is present on a call for heat and the water

heater pump is not operating, replace the pump.

• Replace the main control board.

Rem Ctrl Flt

External control is cycling too often.

• Check set point of the external control.

• Check the wiring between the external control and the

unit.

• Replace the control.

Parameters

Progr

(will require a manual

reset once the condition

has been corrected. Press

the RESET button on the
SMART SYSTEM display

to reset.)

After downloading parameters from a laptop,
the main control board must be reset.

• Press the ENTER/RESET button on the SMART

SYSTEM display panel.