beautypg.com

Troubleshooting – Lochinvar ARMOR 150 - 800 User Manual

Page 26

background image

26

Service Manual

3

Troubleshooting

Table 3E (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Water Heater Interface

FAULT

DESCRIPTION

CORRECTIVE ACTION

No Flame Ign

(will require a manual

reset once the condition

has been corrected.

Press the RESET button

on the SMART SYSTEM

display to reset.)

The unit has failed to prove main burner
ignition after four (4) attempts.

Exception: Models 500 - 800 will lock out
after one retry for ignition. It will require a
manual reset before attempting to fire again.

• Inspect spark electrode and associated wiring for

damage and connection. Reference page 19 of this
manual for removal and cleaning procedures.
Replace if necessary.

• Check for proper electrical grounding of the unit.

• Check incoming supply gas pressure. Natural gas

pressures should be between 4 - 14 inches w.c. and
LP gas pressures should be between 8 - 14 inches w.c.
Refer to Section 7 - Gas Connections of the Armor
Water Heater Installation and Operation Manual for
detailed information concerning the gas supply.

• Verify that the plastic hose from the gas valve to the air

inlet is connected and is not damaged.

• Verify that the vent/air intake pipes are correctly

installed and that there are no obstructions.

• Check for 24 VAC to the gas valve at the 2-pin

connection on the side of the main control board during
the ignition attempt. If no voltage is present, replace
the main control board.

• If 24 VAC is present at the main control board, check

the wiring between the main control board and the gas
valve. Replace the wiring if necessary. Do not
disconnect the wiring from the gas valve and attempt to
measure voltage at that point. The main control board
can detect if the gas valve is not connected and will
display the GV / Relay Fail fault.

• If 24 VAC is present, check the outlet of the valve to

ensure the valve is flowing gas. With a manometer
connected to the outlet tap of the gas valve, when the
unit is in the prepurge period, there should be a
negative pressure present. When the valve is
energized a change in pressure should occur. If the
pressure change does not occur, the gas valve is not
opening. Replace the gas valve.

• Inspect flame sensor and associated wiring.

Reference page 19 of this manual for removal and
cleaning procedures. Replace if necessary.

• Inspect the burner. Reference page 19 of this manual

for removal and cleaning procedures. Replace if
necessary.

• Replace the main control board.