Table 5 battery run times, Table 5, Battery run times – Liebert PowerSure PSI 1000 - 3000VA 60 Hz 120V User Manual
Page 34: Refer to table 5 - battery run, Times

Specifications
28
Table 5
Battery run times
Load%
1000VA
1440VA
1920VA
2200VA
3000VA
Internal Battery
(minutes)
5%
174
138
181
171
177
10%
118
79
104
73
91
20%
65
45
52
47
47
30%
41
28
31
26
28
40%
37
24
25
23
22
50%
26
16
19
16
16
60%
24
14
15
13
14
70%
18
10
11
10
10
80%
16
9
10
8
9
90%
12
6
8
6
7
100%
11
5
6
5
6
Internal Battery
+ 1 External
Battery Cabinet
(minutes)
5%
513
409
575
542
542
10%
305
265
294
266
257
20%
248
188
208
185
148
30%
177
125
143
135
141
40%
139
104
123
122
99
50%
119
72
105
99
67
60%
98
59
82
75
53
70%
75
45
59
55
45
80%
63
40
53
49
39
90%
53
35
47
44
34
100%
46
30
43
40
29
Internal Battery
+ 2 External
Battery Cabinets
(minutes)
5%
1001
828
—
—
—
10%
565
461
590
493
444
20%
409
283
307
291
249
30%
283
219
243
222
168
40%
248
177
197
194
148
50%
209
133
163
150
129
60%
166
122
141
137
114
70%
136
98
128
122
92
80%
127
84
115
107
71
90%
110
64
102
92
56
100%
98
56
89
77
52
Internal Battery
+ 3 External
Battery Cabinets
(minutes)
5%
1174
1001
—
—
—
10%
1001
655
—
590
—
20%
565
409
522
493
300
30%
409
283
298
283
240
40%
305
257
267
266
213
50%
274
209
237
222
168
60%
248
166
197
185
144
70%
209
136
166
156
129
80%
188
125
147
141
116
90%
145
110
138
131
101
100%
136
95
128
120
88
Internal Battery
+ 4 External
Battery Cabinets
(minutes)
5%
1174
—
—
—
—
10%
1174
828
—
—
—
20%
828
565
639
590
444
30%
513
357
458
395
283
40%
461
292
322
300
266
50%
305
257
281
274
222
60%
283
230
252
240
179
70%
257
188
220
203
150
80%
239
156
192
173
139
90%
209
136
169
156
129
100%
188
125
150
144
118
NOTE
Approximate discharge times are in minutes and at 77°F (25°C) with resistive load.