NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

4

INDOOR INSTALLATIONS - The minimum

installed height of the completed fi replace

system for is 15' 0." The maximum height is

60' 0" (see Table 1).

OUTDOOR INSTALLATIONS - The minimum

installed height of the completed fi replace

system is 7' 3." The maximum height is 60"

(see Table 2).

The fi replace and chimney system must be

enclosed when installed in or passing through

a living area where combustibles or people may

come in contact with it. This is important to pre-

vent possible personal injury or fi re hazard.

For questions, please call your distributor or

the manufacturer. Special restrictions apply to

the front and facing of the fi replace and nearby

walls (See Pages 20, 21 & 22).

CHIMNEY SYSTEM

These fi replaces are designed and code listed for

use with Security Chimneys FTF8 chimney Sys-

8

F

T

F

s

y

e

n

m

i

h

C

y

ti

r

u

c

e

S

e

s

u

s

y

a

w

l

A

.

y

l

n

o

m

e

t

chimney components with these fi replaces. Do

not modify or alter these components as this

may cause a potential serious hazard and void

the Warranty.

Chimney Height -

Indoor Installations

The total height of your completed fi replace

system from the surface the fi replace rests on

to the chimney top must not exceed 60' and

must also meet minimum height requirements.

Refer to the minimum system height chart (see

Table 1).

Chimney Height -

Outdoor Installations

The total height of your completed fi replace

system from the surface the fi replace rests on

to the chimney top must not exceed 60' and

must also meet minimum height requirements.

Refer to the minimum system height chart (see

Table 2).

INDOOR INSTALLATIONS

Minimum System Height

Security's FTF8 Pipe

Vertical Installation

15' 0"

One Offsets

15' 0"

Two Offsets

25' 0"

Table 1

OUTDOOR INSTALLATIONS

Minimum System Height

Security's FTF8 Pipe

Vertical Installation

7' 3"

One Offsets

15' 0"

Two Offsets

25' 0"

Table 2

- See following Notes

When complete these fi replace systems consists

of fi ve basic “sub-systems”:

1. The Fireplace

2. The Chimney and Termination

3. The Optional Glass Doors

4. The Optional Outside Air Kits

5. The Optional Weather Cover (for outdoor

installations)

CLEARANCES AND HEIGHT

REQUIREMENTS

The fi replace may be placed on or near normal

construction materials*. The outside air kit,

fi restop spacer and roof fl ashing (not chase

fl ashings) may be placed directly on or against

normal construction materials. **

A combustible mantel may be installed 12"

above the opening of the fi replace as per NFPA

211-latest edition. In Canada, the minimum is

18" above the fi replace opening.

* In the USA, the chimney and fi replace outer

wrapper require a minimum 1"

air space

to insulation and construction materials.

In Canada, the chimney and fi replace outer

wrapper require a minimum 2" air space to

insulation and construction materials.

** Construction Materials:

• Framing Materials • Paneling

• Particle Board

• Flooring

• Dry Wall

• Plywood

• Noncombustible Insulating Materials

• Etc.

Notes (

Table 2

)

• Outdoor fi replace system less than 15 feet

height must be a minimum of 10 feet away

from a building or combustible structure.

The 10 foot rule applies on all cases (see

ten foot rule summary on Page 15).

• The system height may be reduced to a

n

o

it

a

n

i

m

r

e

t

d

n

a

e

p

i

p

8

4

-

8

F

T

F

f

o

h

t

g

n

e

l

e

l

g

n

i

s

with either the FTF8-CTD or FTF8-CTDT for

a minimum height on a complete system of

7' 3." The fi replace must be installed as a

Freestanding system and located a minimum

of 10' away from any building or structure

(refer to Figure 1).

• The minimum height will vary when using

other Firecraft or Lennox Terminations.

Chase Enclosure

A chase is a vertical box-like structure con-

structed to surround the fi replace and chimney.

Refer to Figure 4 for a typical chase confi gura-

tion. As with all chimney installations, avoid

overhead obstructions such as trees, power

lines, etc. A chase should be constructed and

insulated just like any outside wall. In a cold

climate, we recommend the base of the chase

should also be insulated between the solid

continuous fl oor beneath the fi replace and the

chase bottom. Chase insulation in a cold climate

installation is not required for safety.
Note: Do not insulate the chase cavity with

blown or fi ll type insulation materials.
Note: Local codes may not require fi restopping

at the ceiling levels for outside chase installa-

tions. However, it is recommended for safety

and the reduction of heat loss.

WARNING

Failure to use manufacture

provided parts, variations in

techniques and construction

materials or practices other than

those described in this manual

may create a fi re hazard and void

the limited warranty.

AVERTISSEMENT

L’échec d’utiliser la fabrication

les parties fournies, les varia-

tions dans les techniques et le

matériel de construction ou les

pratiques autre que ceux-là ont

décrit dans ce manuel peut créer

un risque d’incendie et un vide

la garantie limitée.

ASSEMBLY OUTLINE

Before You Start

Check your inventory list to be sure you have

all the necessary parts supplied in good us-

able condition. Check also for any concealed

damage.
Check the operation of the damper. Control

the damper by adjusting the damper rod in-

side the top center of the firebox opening,

behind the lintel (see Figure 3, next page).
• To CLOSE the damper, pull the damper rod

FORWARD (toward the front of the fireplace),

then slide LEFT until locked in position.

• To OPEN the damper, pull the damper rod

FORWARD (toward the front of the fireplace),

then slide RIGHT until locked in position.