Attention, Warning, Avertissement – Lennox Hearth MERIT PLUS MP-36OD User Manual
Page 20

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
20
COLD CLIMATE INSULATION
If you live in a cold climate, it is especially 
important to seal all cracks around the fi replace 
opening with noncombustible material and 
wherever cold air could enter the room. Sur-
rounding materials must be caulked where it 
meets the black metal facing of the fi replace to 
avoid cold air intrusion. Use noncombustible 
caulking material only on fi replace facing to seal. 
Also, the outside air inlet duct should be wrapped 
with noncombustible insulation to minimize 
the formation of condensation. Do not place 
insulation materials on top of fi replace or against 
chimney sections. If gas logs are installed, the 
gas line holes and other openings should be 
caulked with high temperature caulk or stuffed 
with unfaced fi berglass insulation. 
Note: A 1"* air space must be preserved for all 
insulation and construction materials extend-
ing for any continuous length adjacent to the 
chimney.
It is especially important to insulate between the 
studs of an outside chase cavity and under the 
fl oor if the fl oor is above ground level. Do not 
place insulation directly against the fi replace 
or chimney system.
FIREPLACE FINISHES
Mantels and Trim
It is sometimes best to frame your fi replace after 
it is positioned and the chimney is installed. 
Frame enclosure for chimney and fi replace with 
2 x 4’s (or heavier) lumber.
Note: The header may touch but not rest its 
weight on the two (2) metal top spacers on top 
of the unit. The header must not be notched to 
fi t around the spacers.
These fi replaces may sit directly on a com-
bustible surface. A 1"* air space is required 
between insulation and building materials 
and the chimney. A 1" air space is required 
between combustible framing and fi replace 
outer wrapper. 
In Canada, the minimum height for a combus-
tible mantel is 18" (457 mm) above the fi replace 
opening. Figure 51 shows typical Canadian 
installations. Combustible mantels and trim 
may be installed 12" above the fi replace opening 
as per NFPA 211-latest edition and Figure 52. 
If a mantel is of a noncombustible material, 
it is exempt from these requirements as long 
as it does not interfere with the installation or 
operation of glass doors.
*Note: 2" clearance to combustibles required 
in Canada.
Note: Do not place any combustible materials 
on the fi replace face.
Figure 52 -
Typical Installation
12"*
Min. 9-5/8"*
Min.
Fireplace
Opening
Spacer
Combustible
Mantel
and Trim
12"
Max.
1 1/2"
Finished
Wall
Header
*Both Of These Dimensions Must Be At Least 18”
When An Unvented Gas Log Set Rated At 26,000
BTU Or Higher Is Used. (Maximum 40,000 BTU).
❂
1-5/8" Min.
❂
The shaded gray area showing 1-5/8" Min.
indicates non-combustible materal is required.
Hearth Extensions and Wall Shields
A hearth extension must be installed with 
all fi replaces. It is to protect the combustible 
fl oor in front of the fi replace from both radiant 
heat and sparks. The hearth extension must 
extend 8" beyond both sides of the fi replace 
opening and 16" beyond the front (see Figure 
53). Use a hearth extension constructed of a 
durable noncombustible material having an 
equal or better (lower k value) insulating value of 
k = .84 BTU IN/FT
2
HR °F or a thermal resistance
that equals or exceeds r = 1.19 HR °F FT
2
/BTU
IN. With these values, determine the minimum 
thickness/material required using the formula 
and Table 5 on Page 21.
Note: Any noncombustible material having 
a thickness of 1" whose k value is less than 
.84 or whose r value is more than 1.19 is ac-
ceptable.
If the fi replace is installed on a combustible 
fl oor, use the metal safety strips (provided) 
on the fl oor extending half under the fi replace 
and half under the hearth extension (refer to 
Figures 21 & 22).
A wall shield is required where a continuous 
perpendicular side wall is within 12" of the 
fi replace opening (Figure 53). Use a 24" W x 
30" H x 1/2" wall shield constructed of a durable, 
noncombustible material having an equal or 
better (lower k value) insulating value than 
k = .54 BTU IN/FT
2
HR °F. At no time may a
perpendicular side wall be located closer than 
7" from the fi replace opening.
If fi replace is installed diagonally across a 90° 
corner; no wall shields are required.
Fireplace
Opening
Top Spacer
on Appliance
Combustible
Mantel
8" Max.
(203mm)
Finished
Wall
Header
18" Max.
❂
1-5/8" Min.
(457mm)
❂
The shaded gray area showing 1-5/8" Min.
indicates non-combustible materal is required.
ATTENTION
Certaines portes de verre recou-
vrent le revêtement noir en métal 
du foyer. SI la façade du foyer a 
été recouverte avec des matériaux 
non-combustibles, il se pourrait 
qu’il n’y ait pas suffi sament de 
dégagement pour installer les 
portes de verre de votre choix. 
Assurez d’avoir un dégagmet suf-
fi sant à tout moment afi n de ne 
pas interférer avec l’installation et 
l’opération des portes de verre.
Figure 51 -
Canadian Installation
WARNING
Only non-combustible materials 
are allowed on front face (front 
fi replace frame) and around the 
perimeter within 1-5/8" minimum 
on top and 1/2" on sides.
AVERTISSEMENT
Seulement on permet des matéri-
aux non-combustibles sur le visage 
avant (armature avant de chemi-
née) et autour du périmètre à moins 
de 1-5/8 pouces sur le dessus et 
de pouce de 1/2 des côtés.
