Table 11 external battery cabinet specifications, 1 product warranty registration, Product warranty registration – Liebert GXT2-6000 RT208 User Manual
Page 49: Table 11, External battery cabinet specifications
![background image](/manuals/166912/49/background.png)
Specifications
43
14.1 Product Warranty Registration
To register for warranty protection:
• Visit the Quick Links section of our Web site at:
• Click on Product Warranty Registration and fill in the form.
If you have any questions, please contact us at:
US: 800-222-5877
Outside the US: 614-841-6755
Table 11
External battery cabinet specifications
Model Number
GXT2-144VBATT
Used w/ UPS Model
GXT2-6000RT208
DIMENSIONS in (mm)
Unit (with bezel) W x D x H
3.5 x 24.2 x 17 (87 x 618 x 430)
Shipping W x D x H
10.5 x 27.2 x 23 (268 x 692 x 585)
WEIGHT lbs (kg)
Unit
93.6 (42.5)
Shipping
105 (47.6)
BATTERY PARAMETERS
Type
Valve-regulated, non-spillable, flame retardant, lead acid
Qty x V x Rating
12 x 12V x 9.0 AH
Battery Mfg / Part #
Yuasa / REW 45-12 FR
Back-Up Time
See Table 7 - Battery run times
ENVIRONMENTAL
Operating Temp
+32°F to +104°F (0°C to +40°C)
Storage Temp
+5°F to +122°F (-15°C to +50°C)
Relative Humidity
0% to 95%, non-condensing
Operating Elevation
Up to 10,000 ft. (3000m) at 104°F (40°C) without derating
Storage Elevation
50,000 ft. (15,000m) maximum
AGENCY
Safety
UL 1778, c-UL Listed (Suitable for computer room applications)
RFI/EMI
FCC Part 15, Subpart B, Class A
Transportation
ISTA Procedure 1A