Determine boiler location, Installation & service manual – Lochinvar 000 - 500 User Manual

Page 13

background image

1

Determine boiler location

(continued)

13

Installation & Service Manual

TABLE - 1B

MINIMUM RECOMMENDED COMBUSTION

AIR SUPPLY TO EQUIPMENT ROOM

Input

Btu/hr

*Outside Air from

2 Openings Directly from

Outdoors

*Outside Air from

1 Opening Directly

from Outdoors, in

2

*Outside Air from

2 Ducts Delivered from

Outdoors

**Inside Air from

2 Ducts Delivered from

Interior Space

Top

Opening, in

2

Bottom

Opening, in

2

Top

Opening, in

2

Bottom

Opening, in

2

Top

Opening, in

2

Bottom

Opening, in

2

90,000

23

(148 cm

2

)

23

(148 cm

2

)

30

(194 cm

2

)

45

(291 cm

2

)

45

(291 cm

2

)

100

(646 cm

2

)

100

(646 cm

2

)

135,000

34

(220 cm

2

)

34

(220 cm

2

)

45

(291 cm

2

)

68

(439 cm

2

)

68

(439 cm

2

)

135

(871 cm

2

)

135

(871 cm

2

)

180,000

45

(291 cm

2

)

45

(291 cm

2

)

60

(388 cm

2

)

90

(581 cm

2

)

90

(581 cm

2

)

180

(1,162 cm

2

)

180

(1,162 cm

2

)

199,999

50

(323 cm

2

)

50

(323 cm

2

)

67

(433 cm

2

)

100

(646 cm

2

)

100

(646 cm

2

)

200

(1,291 cm

2

)

200

(1,291 cm

2

)

225,000

57

(368 cm

2

)

57

(368 cm

2

)

75

(484 cm

2

)

113

(730 cm

2

)

113

(730 cm

2

)

225

(1,452 cm

2

)

225

(1,452 cm

2

)

270,000

68

(439 cm

2

)

68

(439 cm

2

)

90

(581 cm

2

)

135

(871 cm

2

)

135

(871 cm

2

)

270

(1,742 cm

2

)

270

(1,742 cm

2

)

315,000

79

(510 cm

2

)

79

(510 cm

2

)

105

(678 cm

2

)

158

(1,020 cm

2

)

158

(1,020 cm

2

)

315

(2,033 cm

2

)

315

(2,033 cm

2

)

360,000

90

(581 cm

2

)

90

(581 cm

2

)

120

(775 cm

2

)

180

(1,162 cm

2

)

180

(1,162 cm

2

)

360

(2,323 cm

2

)

360

(2,323 cm

2

)

399,999

100

(646 cm

2

)

100

(646 cm

2

)

134

(865 cm

2

)

200

(1,291 cm

2

)

200

(1,291 cm

2

)

400

(2,581 cm

2

)

400

(2,581 cm

2

)

500,000

125

(807 cm

2

)

125

(807 cm

2

)

167

(1,078 cm

2

)

250

(1,613 cm

2

)

250

(1,613 cm

2

)

500

(3,226 cm

2

)

500

(3,226 cm

2

)

*Outside air openings shall directly communicate with the outdoors. When combustion air is drawn from the outside through a
duct, the net free area of each of the two openings must have twice (2 times) the free area required for Outside Air/2 Openings.
The above requirements are for the boiler only; additional gas fired appliances in the equipment room will require an increase in
the net free area to supply adequate combustion air for all appliances.

**Combined interior space must be 50 cubic feet per 1,000 Btu/hr input. Buildings MUST NOT be of *“Tight Construction”.
For buildings of *“Tight Construction”, provide air openings into the building from outside.

*No combustion air openings are needed when the water heater is installed in a space with a volume NO LESS than 50 cubic feet
per 1,000 Btu/hr of all installed gas fired appliances. Buildings MUST NOT be of *“Tight Construction”.

* “Tight Construction” is defined as a building with less than 0.40 ACH (air changes per hour).

Vent installations for connection to gas vents or
chimneys must be in accordance with “Vent

ing of

Equipment,” of the latest edition of the Na tion al Fuel Gas
Code, ANSI Z223.1, in Canada, the latest edi tion of CGA
Standard B149 Installation Code for Gas Burning Appliances
and Equipment or applicable pro vi sions of the local building
codes.

Adequate combustion and ventilation air must be
sup

plied to the room where the appliance is installed in

accordance with the latest edition of the National Fuel Gas
Code, ANSI Z223.1, in Canada, the latest edition of CGA
Standard B149 Installation Code for Gas Burning Ap pli anc es
and Equipment, or applicable pro vi sions of the local building
codes.