Installation & Operation Manual

Table 6A Natural Gas Pipe Size Chart

The gas piping must be sized for the proper flow and length of
pipe, to avoid excessive pressure drop. Both the gas meter and
the gas regulator must be properly sized for the total gas load.

If you experience a pressure drop greater than 1 inch w.c.
(249 Pa), the meter, regulator, or gas line is undersized or in
need of service. Perform the steps below when checking inlet
gas supply:

1.

Turn the main power switch to the “OFF” position.

2.

Shut off gas supply at the manual gas valve in the gas
piping to the appliance.

3.

Remove the 1/8" pipe plug on the flange to the field
supplied gas shutoff valve and install a suitable 1/8"
fitting (field supplied) for the manometer tubing. Place the
tubing of the manometer over the tap once the 1/8"
fitting is installed as shown in FIG. 6-3.

4.

Slowly turn on the gas supply at the field installed
manual gas valve.

5.

Turn the power switch to the “ON” position.

6.

Adjust the temperature set point on the control panel of
the SMART TOUCH control module to call for heat.

7.

Observe the gas supply pressure as the burner fires at
100% of rated input. Percent of burner input will be
displayed on the Burner Screen.

8.

Ensure inlet pressure is within specified range.
Minimum and maximum gas supply pressures are
specified in this section of the manual.

9.

If gas supply pressure is within normal range and no
adjustments are needed, proceed on to Step 11.

10. If the gas pressure is out of range, contact the gas utility,

gas supplier, qualified installer or service agency to
determine the necessary steps to provide proper gas
pressure to the control.

11. Turn the power switch to the “OFF” position.

12. Shut off the gas supply at the manual gas valve in the gas

piping to the appliance.

13. Remove the manometer from the pressure tap on top of

the gas valve. Remove the 1/8" (3 mm) field supplied
fitting and reinstall the pipe plug removed in Step 3.

NOTICE

CSA or UL listed flexible gas connections are
acceptable, but you must exercise caution to
ensure that the line has adequate capacity to
allow your boiler to fire at full rate. Consult
with local codes for proper installation or
service procedures.

DO NOT adjust or attempt to measure gas
valve outlet pressure. Attempting to alter or
measure the gas valve outlet pressure could
result in damage to the valve, causing
potential severe personal injury, death, or
substantial property damage.

ƽ WARNING

TABLE - 6A

GAS PIPING SIZE CHART

Nominal

Iron Pipe

Size

Inches

Length of Pipe in Straight Feet

Maximum

Capacity of Pipe

in Thousands of

Btu/hr for gas

pressures of

14 Inches Water

Column (0.5

PSIG) or less and

a pressure drop

of 0.5 Inch Water

Column (Based

on NAT GAS,

1025 Btu/hr per

Cubic Foot of

Gas and 0.60

Specific Gravity)

10

20

30

40

50

60

70

80

90

100

125

150

175

200

2,150

1,500

1,210

1,020

923

830

769

707

666

636

564

513

472

441

2

4,100

2,820

2,260

1,950

1,720

1,560 1,440 1,330

1,250

1,180

1,100

974

871

820

6,460

4,460

3,610

3,100

2,720

2,460 2,310 2,100

2,000

1,900

1,700 1,540 1,400

1,300

3

11,200

7,900

6,400

5,400

4,870

4,410 4,000 3,800

3,540

3,300

3,000 2,720 2,500

2,340

4

23,500 16,100 13,100 11,100 10,000 9,000 8,300 7,690

7,380

6,870

6,150 5,640 5,130

4,720

Check inlet gas supply

33

6

Gas connections

(continued)