115v specifications – Liebert 115V User Manual
Page 8

8
115V SPECIFICATIONS
Model Number
PSA350-120
PSA470-120
PSA700-120
Model Rating VA/W
350VA/210W
470VA/282W
700VA/420W
DIMENSIONS: in (mm)
Unit
H x W x D
6.5 x 4.5 x 13.9
(166 x 115.5 x 352.5)
6.5 x 4.5 x 13.9
(166 x 115.5 x 352.5)
6.5 x 4.5 x 13.9
(166 x 115.5 x 352.5)
Shipping
H x W x D
8.8 x 6.2 x 15.8
(226 x 156 x 404)
8.8 x 6.2 x 15.8
(226 x 156 x 404)
8.8 x 6.2 x 15.8
(226 x 156 x 404)
WEIGHT: lbs (kg)
Unit
13.2 (6)
15.4 (7)
22 (10)
Shipping
15 (6.8)
17.2 (7.8)
23.8 (10.8)
INPUT AC PARAMETERS
Voltage Range
without Battery Operation
87 to 144VAC
Line to Boost Transfer
104VAC
Line to Buck Transfer
124VAC
Frequency
47-53 Hz or 57-63 Hz; auto sensing
Input Power Cord
6 ft. detachable, w/ NEMA 5-15 P
OUTPUT AC PARAMETERS
Output Receptacles
(4) 5-15R
Voltage (Battery Mode)
115 VAC + 5%
Waveform (Battery Mode)
Stepped Sinewave
Voltage (Normal)
V
IN
* (1.0)
Voltage (Boost Mode)
V
IN
* (1.16)
Voltage (Buck Mode)
V
IN
* (0.84)
Frequency
50 Hz or 60 Hz; auto sensing
Overload Warning
(Utility and Battery Modes)
101 – 120%
Overload Shutdown
(Utility and Battery Modes)
Overload
+ (15 – 30W)
Overload
+ (20 – 40W)
Overload
+ (30 – 60W)
BATTERY PARAMETERS
Type
Valve-regulated, nonspillable, lead acid
Quantity x Voltage x Rating
(1) x 12V x 7.0 Ah
(1) x 12V x 7.0 Ah
(1) x 12V x 10 Ah
Approved Battery
Manufacturers:
CSB, Panasonic, and Yuasa
Transfer Time
4 – 6 ms typical
At 77°F (25°C), resistive loading, with fully charged batteries:
> 5 minutes typical
Back-up Time:
Full load
Half load
> 15 minutes typical
> 12 minutes typical
> 13 minutes typical
Recharge Time
7-10 hours to 90% capacity, after full discharge into 100% resistive load
ENVIRONMENTAL
Operating Temperature
+32° F to + 104° F (0° C to +40° C)
Storage Temperature
+5° F to + 122° F (-15° C to +50° C)
Relative Humidity
0% to 90%, non-condensing
Operating Elevation
Up to 10,000 ft. (3000 m) at 95° F (35° C) without derating
Audible Noise
< 40 dBA, at 1 meter
AGENCY
Safety
UL 1778, c-UL Listed
Surge
IEEE C62.41 Category A
ESD
IEC 801-2, Level 3, Criterion< 2
Susceptibility
IEC 801-3, Level 3, Criterion< 2
Electrical Fast Transient/Burst
IEC 801-4, Level 4, Criterion< 2
Emissions
FCC Part 15, Subpart B, Class B
Transportation
ISTA Project 1A