Specifications, 2 and 3 ton split systems – Liebert Overhead Precision Cooling and Humidity Control Mini-Mate2 User Manual
Page 9

60 HZ
50 HZ
CHILLED WATER
3 Tons
3 Tons
Evaporator
MMD40C
MMD39C
Capacity Data BTUH (kW) High Fan Speed
80 F (26.7 C) DB
Total
49,200 (14.4)
49,200 (14.4)
50% RH
Sensible
33,100 (9.7)
33,100 (9.7)
75 F (23.9 C) DB
Total
33,900 (9.9)
33,900 (9.9)
50% RH
Sensible
27,800 (8.1)
27,800 (8.1)
72 F (22.2 C) DB
Total
27,100 (7.9)
27,100 (7.9)
50% RH
Sensible
24,900 (7.3)
24,900 (7.3)
Capacity Data BTUH (kW) Low Fan Speed
80 F (26.7 C) DB
Total
40,700 (11.9)
40,700 (11.9)
50% RH
Sensible
26,900 (7.9)
26,900 (7.9)
75 F (23.9 C) DB
Total
27,700 (8.1)
27,700 (8.1)
50% RH
Sensible
22,300 (6.5)
22,300 (6.5)
72 F (22.2 C) DB
Total
21,700 (6.4)
21,700 (6.4)
50% RH
Sensible
19,800 (5.8)
19,800 (5.8)
60 HZ
50 HZ
AIR COOLED SYSTEM
with Outdoor Condensing Unit
with Centrifugal Condensing Unit
with Outdoor Condensing Unit with Centrifugal Condensing Unit
2 Tons
3 Tons
2 Tons
3 Tons
2 Tons
3 Tons
2 Tons
3 Tons
Evaporator
MMD24E
MMD36E
MMD24E
MMD36E
MMD23E
MMD35E
MMD23E
MMD35E
Condensing Unit
PFH027A
PFH037A
MCD24A
MCD36A
PFH026A
PFH036A
MCD23A
MCD35A
Net Capacity Data*BTUH (kW) High Fan Speed
80 F (26.7 C) DB
Total
25,600 (7.5) 36,900 (10.8)
24,200 (7.1) 34,100 (10.0) 23,800 (7.0)
34,500 (10.1) 22,700 (6.7)
31,800 (9.3)
50% RH
Sensible
20,900 (6.1)
26,600 (7.8)
20,300 (5.9)
28,300 (8.3)
20,200 (5.9)
28,400 (8.3)
19,800 (5.8)
27,400 (8.0)
75 F (23.9 C) DB
Total
23,800 (7.0) 34,200 (10.0)
22,400 (6.6)
31,700 (9.3)
22,100 (6.5)
32,100 (9.4)
21,000 (6.2)
29,600 (8.7)
50% RH
Sensible
20,100 (5.9)
25,700 (7.5)
19,500 (5.7)
27,200 (8.0)
19,400 (5.7)
27,400 (8.0)
19,000 (5.6)
26,400 (7.7)
72 F (22.2 C) DB
Total
22,900 (6.7)
32,900 (9.6)
21,400 (6.3)
30,400 (8.9)
21,200 (6.2)
30,800 (9.0)
20,100 (5.9)
28,300 (8.3)
50% RH
Sensible
19,700 (5.8)
25,200 (7.4)
19,100 (5.6)
26,500 (7.8)
19,000 (5.6)
26,700 (7.8)
18,500 (5.4)
25,700 (7.5)
Net Capacity Data*BTUH (kW) Low Fan Speed
80 F (26.7 C) DB
Total
25,500 (7.5) 36,900 (10.8)
24,000 (7.0)
33,600 (9.8)
23,700 (6.9)
34,000 (10.0) 22,600 (6.6)
31,500 (9.2)
50% RH
Sensible
19,800 (5.8)
26,600 (7.8)
19,300 (5.7)
25,300 (7.4)
19,100 (5.6)
25,400 (7.4)
18,700 (5.5)
24,400 (7.1)
75 F (23.9 C) DB
Total
23,800 (7.0) 34,200 (10.0)
22,300 (6.5)
31,300 (9.2)
22,000 (6.4)
31,700 (9.3)
20,900 (6.1)
29,300 (8.6)
50% RH
Sensible
19,200 (5.6)
25,700 (7.5)
18,500 (5.4)
24,300 (7.1)
18,400 (5.4)
24,600 (7.2)
18,000 (5.3)
23,600 (6.9)
72 F (22.2 C) DB
Total
22,700 (6.7)
32,900 (9.6)
21,300 (6.2)
29,900 (8.8)
21,100 (6.2)
30,400 (8.9)
20,000 (5.9)
28,000 (8.2)
50% RH
Sensible
18,700 (5.5)
25,200 (7.4)
18,100 (5.3)
23,900 (7.0)
18,000 (5.3)
24,100 (7.1)
17,500 (5.1)
23,100 (6.8)
60 HZ
50 HZ
WATER COOLED
GLYCOL COOLED
WATER COOLED
GLYCOL COOLED
2 Tons
3 Tons
2 Tons
3 Tons
2 Tons
3 Tons
2 Tons
3 Tons
Evaporator
MMD24E
MMD36E
MMD24E
MMD36E
MMD23E
MMD35E
MMD23E
MMD35E
Condensing Unit
MCD26W
MCD38W
MCD26W
MCD38W
MCD25W
MCD37W
MCD25W
MCD37W
Net Capacity Data*BTUH (kW) High Fan Speed
80 F (26.7 C) DB
Total
26,600 (7.8) 38,400 (11.3)
23,000 (6.7) 35,200 (10.3) 24,900 (7.3)
35,700 (10.5) 21,300 (6.2)
32,600 (9.6)
50% RH
Sensible
21,300 (6.2)
29,900 (8.8)
19,900 (5.8)
28,700 (8.4)
20,600 (6.0)
28,900 (8.5)
19,300 (5.7)
27,700 (8.1)
75 F (23.9 C) DB
Total
24,600 (7.2) 35,600 (10.4)
21,400 (6.3)
32,700 (9.6)
22,800 (6.7)
33,000 (9.7)
19,800 (5.8)
30,400 (8.9)
50% RH
Sensible
20,400 (6.0)
28,800 (8.4)
19,100 (5.6)
27,600 (8.1)
19,700 (5.8)
27,700 (8.1)
18,500 (5.4)
26,700 (7.8)
72 F (22.2 C) DB
Total
23,400 (6.9)
33,900 (9.9)
20,500 (6.0)
31,300 (9.2)
21,800 (6.4)
31,500 (9.2)
18,700 (5.5)
29,100 (8.5)
50% RH
Sensible
19,900 (5.8)
28,100 (8.2)
18,700 (5.5)
27,000 (7.9)
19,200 (5.6)
27,100 (7.9)
18,700 (5.5)
26,000 (7.6)
Net Capacity Data*BTUH (kW) Low Fan Speed
80 F (26.7 C) DB
Total
26,200 (7.7) 37,400 (11.0)
22,700 (6.7) 34,200 (10.0) 24,500 (7.2)
34,600 (10.1) 21,100 (6.2)
31,800 (9.3)
50% RH
Sensible
20,100 (5.9)
26,700 (7.8)
18,800 (5.5)
25,500 (7.5)
19,500 (5.7)
25,700 (7.5)
18,200 (5.3)
24,600 (7.2)
75 F (23.9 C) DB
Total
24,200 (7.1) 34,400 (10.1)
21,100 (6.2)
31,800 (9.3)
22,600 (6.6)
32,000 (9.4)
19,600 (5.7)
29,600 (8.7)
50% RH
Sensible
19,400 (5.7)
25,800 (7.6)
18,100 (5.3)
24,700 (7.2)
18,700 (5.5)
24,800 (7.3)
17,500 (5.1)
23,700 (6.9)
72 F (22.2 C) DB
Total
23,000 (6.7)
32,900 (9.6)
20,300 (5.9)
30,500 (8.9)
21,500 (6.3)
30,600 (9.0)
18,800 (5.5)
28,300 (8.3)
50% RH
Sensible
18,900 (5.5)
25,200 (7.4)
17,700 (5.2)
24,100 (7.1)
18,200 (5.3)
24,200 (7.1)
17,000 (5.0)
23,200 (6.8)
*The net capacity data has fan motor heat factored in for all ratings and the entering air condition of 72˚F (22.2˚C), 50% RH is the standard rating condition of ASHRAE 127-2001
9
Specifications
2 And 3 Ton Split Systems