Voltage lockout, Load lockout, Logic failure – Liebert Series 610 User Manual
Page 28: Lamp test, 5 manual controls, Close load 1, Close load 2, Trip load 1, Trip load 2, Trip tie
Control Panel Description
24
Voltage Lockout
This light indicates the system voltages are too far apart to allow safe transfers and parallel operation
of the UPS systems. To correct this condition, adjust the UPS system voltage to proper levels.
If both system voltages are adjusted correctly, and the PHASE LOCKOUT alarm is not present, then
check the voltage detection circuitry. Contact Liebert Global Services for assistance.
Load Lockout
This light indicates insufficient UPS capacity to perform the selected operation. The control logic
intelligently checks the UPS systems and the Loads based on the specific operation in progress.
Verify UPS capacity and shed load as necessary until UPS capacity is not being exceeded. If UPS
capacity is sufficient, then check the load/capacity detection circuitry. Contact Liebert Global Services
for assistance.
Logic Failure
This light indicates that a logic failure has occurred. No Tie operations are allowed while this condi-
tion exists.
Check all tie control logic functions to determine the source of the fault. Contact Liebert Global Ser-
vices for assistance.
Lamp Test
This button is pressed to check all indicators on the MIMIC and CONTROL PANEL.
3.5
Manual Controls
These controls are located on a panel behind the Control Panel door. They are provided to assist in
initial system start-up and provide emergency manual breaker trip capability. During normal opera-
tions they should not need to be used.
Close Load 1
This button closes the Load 1 circuit breaker during start-up. It only functions if the Tie breaker is
open.
Close Load 2
This button closes the Load 2 circuit breaker during start-up. It only functions if the Tie breaker is
open.
Trip Load 1
This button is used to manually trip the Load 1 circuit breaker and is provided for emergency pur-
poses.
The light on this push button will go out when load is being supplied through the breaker. Pressing
this button when the light is out will result in loss of power to an on-line load.
Trip Load 2
This button is used to manually trip the Load 2 circuit breaker and is provided for emergency pur-
poses.
The light on this push button will go out when load is being supplied through the breaker. Pressing
this button when the light is out will result in loss of power to an on-line load.
Trip Tie
This button is used to manually trip the Tie circuit breaker and is provided for emergency purposes.