Troubleshooting & repair, Retest after repair – Lincoln Electric VANTAGE 400 User Manual
Page 152
TROUBLESHOOTING & REPAIR
F-104
F-104
VANTAGE® 400
RETEST AFTER REPAIR
Retest a machine:
• If it is rejected under test for any reason that requires you to remove any mechanical part which could affect the
machine’s electrical characteristics. OR
• If you repair or replace any electrical components.
ENGINE OUTPUT
Mode
No Load RPM
Load RPM
Low Idle
1300 - 1400
N/A
High Idle
1860 - 1890
1800
WELDER DC (STICK) OUTPUT (ARC control @ -10)
Mode Selector
Output Control
Open Circuit
Load Volts
Load Amps
Switch
Volts
Stick (CC)
Maximum
55-60
36-38
400
WELDER CV (WIRE) OUTPUT (ARC Control @ +10)
Mode Selector
Output Control
Open Circuit
Load Volts
Load Amps
Switch
Voltage
CV
Maximum
55-60
36-38
290-310
CV
Minimum
55-60
17-19
220
TOUCH START TIG (ARC Control @ +10)
Mode Selector
Output Control
Open Circuit
Load Volts
Load Amps
Switch
Voltage
TIG
Maximum
10-15
18-22
240-260
TIG
Minimum
10-15
Short Circuit
18-28
AUXILIARY POWER OUTPUT
240 Volt Receptacle
120 Volt Receptacles
Open Circuit
Load Volts
Load Amps
Open Circuit
Load Volts
Load Amps
Voltage
Voltage
230-264*
216-252
50
115-132
108-126
20
* Upper limit reflects cold machine, voltage will be below 132/264 for machine at normal operating temperature.
42 VOLT WIRE FEEDER POWER
Open Circuit Voltage
Load Volts
Load Amps
40-50
38-48
8=.5