beautypg.com

Troubleshooting – Lochinvar 1.3 User Manual

Page 47

background image

3

Troubleshooting

(continued)

47

Service Manual

Table 3F Troubleshooting Chart - Fault Messages Displayed on Boiler Interface

FAULT

DESCRIPTION

CORRECTIVE ACTION

Gas Pressure

Switch

(will require a manual

reset once the condition

has been corrected.

Press the RESET button

on the display to reset.)

Either the manual reset low gas pressure
switch or the manual reset high gas
pressure switch tripped.

• Reset the pressure switches.

• Measure the supply gas pressure to determine cause

of failure. Natural gas pressures should be between
4 - 14 inches w.c. (1.0 - 3.5 kPa) and LP gas
pressures should be between 8 - 14 inches w.c.
(2.0 - 3.2 kPa).

• Refer to Section 6 - Gas Connections of the SYNC

Installation and Operation Manual for detailed
information concerning the gas supply.

• Correct the supply gas pressure if necessary.

• Check for a loose or misplaced jumper if pressure

switches are not installed.

Flow

Switch/LWCO

(will require a manual

reset once condition has

been corrected. Press
the RESET button on

the display to reset.)

Either the low water cutoff or the optional
flow switch is not making.

• Check boiler pump operation on a call for heat.

• Check for closed valves or obstructions in the boiler

piping.

• Verify system is full of water and all air has been

purged from the system.

• Check for loose or misplaced jumpers if flow switch is

not installed.

Blown fuse.

• Replace fuse F2 on the control board, see page 43 of

this manual.

Condensate

Drain Blocked

(will require a manual

reset once condition has

been corrected. Press
the RESET button on

the display to reset.)

The blocked drain switch has detected
excessive condensate build up inside the
unit.

• Check condensate tube from unit to floor drain for

proper installation and obstructions.

• Inspect condensate trap for blockage. Clean if

necessary.

• Check for loose wiring connection at wire harness

plug.

• Bad blocked drain switch. Replace switch.

Flame out of

Sequence

(will require a manual

reset once the condition

has been corrected.

Press the RESET button

on the display to reset.)

The flame detector circuit is seeing a flame
signal while no flame is present.

• Check supply voltage for proper polarity.

• Check external wiring for voltage feedback.

• Check the flame rod and make sure it is clean.

• Check the internal wiring for bad connections.

• Replace main control board.

Gas Valve /

Connection

(will require a manual

reset once the condition

has been corrected.

Press the RESET button

on the display to reset.)

The main control board did not detect the
gas valve.

• Check wiring harness connection at the gas valve and

at the main control board.

• Replace the gas valve wire harness.

• Replace the gas valve.

• Replace the main control board.