Troubleshooting – Lochinvar EnergyRite ER152 User Manual

Page 24

background image

3

Troubleshooting

24

Service Manual

Table 3C Troubleshooting Chart - Noisy System

FAULT

CAUSE

CORRECTIVE ACTION

Noisy

Operation

- Supply gas problem. Natural gas pressures

should be between 4.0 inches w.c. and
14 inches w.c. LP gas pressures should
be between 8.0 inches w.c. and
14 inches w.c.

• Refer to Section 6 - Gas Connections of the EnergyRite

Installation and Operation Manual for detailed
information concerning the gas supply.

- Dirty / damaged burners.

• Refer to page 16 in this manual for the burner removal

and inspection procedure. Clean or replace the burner
as necessary.

- Low water flow through the heat exchanger. • Refer to Section 7 - Water Connections of the

EnergyRite Installation and Operation Manual for
minimum flow rates. Verify the pool heater pump is
running on a call for heat.

- Air in the piping system.

• Properly purge all air from the piping system.

Relief Valve

Opening

- System pressure exceeds relief valve

setting.

• Lower the system pressure below the 50 PSI rating of

the supplied relief valve or replace the standard relief
valve with a higher rated valve up to the maximum
pressure of the heat exchanger.