115v specifications – Liebert PowerSure Personal User Manual
Page 10
10
115V SPECIFICATIONS
Model Number
PSP300-115
PSP500-115
Model Rating VA / W
300 / 180
500 / 300
DIMENSIONS: in (mm)
Unit H x W x D
7.0 x 3.0 x 9.4
(178 x 76 x 238)
7.0 x 3.0 x 9.4
(178 x 76 x 238)
Shipping H x W x D
10.6 x 4.3 x 12.3
(270 x 110 x 312)
10.6 x 4.3 x 12.3
(270 x 110 x 312)
WEIGHT: lbs (kg)
Unit
6.2 (2.8)
8.0 (3.6)
Shipping
7.7 (3.5)
9.5 (4.3)
INPUT AC PARAMETERS
Voltage Range
without Battery Operation
90-132 VAC
Low Line Transfer
90 VAC
High Line Transfer
132 VAC
Frequency
45-55 Hz or 54-66 Hz; auto sensing
Input Power Cord
6 ft. detachable, w/ NEMA 5-15 P
OUTPUT AC PARAMETERS
Output Receptacles
(4) 5-15R
Voltage (Battery Mode)
115 VAC + 5%
Output Current
2.6 A
4.3 A
Waveform (Battery Mode)
Stepped Sinewave
Frequency
50 Hz or 60 Hz; auto sensing
Overload Warning
(Utility and Battery Modes)
101 – 120%
Overload Shutdown
(Utility and Battery Modes)
Overload Warning
+ (15 – 25 W)
Overload Warning
+ (20 – 45 W)
BATTERY PARAMETERS
Type
Valve-regulated, nonspillable, lead acid
Quantity x Voltage x
Rating
(1) x 12V x 4.5 Ah
(1) x 12V x 7.0 Ah
Approved Battery
Manufacturers:
CSB, Panasonic, BB Battery, and Yuasa
Transfer Time
2 – 6 ms typical
At 77°F (25°C), resistive loading, with fully charged batteries:
> 4 minutes
Back-up Time:
Full load
Half load
12 minutes
Recharge Time
7-10 hours to 90% capacity, after full discharge into 100% resistive
load
ENVIRONMENTAL
Operating Temperature
+32° F to + 104° F (0° C to +40° C)
Storage Temperature
+5° F to + 122° F (-15° C to +50° C)
Relative Humidity
0% to 90%, non-condensing
Operating Elevation
Up to 10,000 ft. (3000 m) at 95° F (35° C) without derating
Audible Noise
< 40 dBA, at 1 meter
AGENCY
Safety
UL 1778, c-UL Listed
Surge
IEEE C62.41 Category A
ESD
IEC 801-2, Level 3, Criterion< 2
Susceptibility
IEC 801-3, Level 3, Criterion< 2
Electrical Fast
Transient/Burst
IEC 801-4, Level 4, Criterion< 2
Emissions
FCC Part 15, Subpart B, Class B
Transportation
ISTA Project 1A