Operation 31

Figure 28 Equalize voltage and duration settings

Fuses

Thirty-four fuses for circuit protection as described in Table 37. Except for the ABS fuse, which is

small tube type (9/32” dia x 1-1/4” long), all fuses are of the QFF type.

Test points

Three sets of test points for applications as described in Table 38.

Table 37

Fuse

Designation

Capacity

Description

ABS

15 A

-48 V supply for the office alarm circuit(s)

ABS ALM

1/2 A

Alarm fuse for the above ABS fuse

RC1 to RC24

1-1/3 A

-48 V sense supply for the rectifiers of the system

CONV

1/2 A

Protection for the internal converter in the controller

METER

1/2 A

Protection for the meter and selector panel if so equipped

CHG

1/2 A

Protection for internal circuitry of the controller when the CONT rotary switch
is in the CHG VOLT position

Spare 1 and 2

0 to 5 A

For external loads as required (ex.: Helios Monitor)

BAT

1/2 A

Protection for internal circuitry of the controller when the CONT rotary switch
is in the BAT VOLT position

CONT

1-1/3 A

Protection for the internal circuitry of the controller

Plus one unused position

Table 38

Test points

Designation

Description

CAL OUT + and -

To connect an external meter when calibrating the LED readout for current readings

VOLT + and -

To connect an external meter when adjusting the BOD, LF, LV, HF, HV, HVSD, LVD and
LVR thresholds

PWR EXT + and -

The connect an external power supply when adjusting the LVR threshold

VOLT

Switch # 1 2 3

0.6V

1.3V

1.9V

2.6V

3.2V

3.9V

4.6V

: switch in the ON position

TIMER

Switch # 1 2 3 4 5 6

10 sec.

20 sec.

38 sec.

1.25 h

3.0 h

5.0 h

LOP enabled

1

2

3

4

5

6

OFF ON

ON OFF

1

2

3