3 distribution panels, 1 fuse panels, Mechanical specifications of the fuse panels – Liebert 1500 User Manual
Page 14: Distribution panels, Fuse panels, Figure 5, Front view of the 20 qff 0-5 a fuse panels, Table 6, Table 7

8 Specifications
3.3
Distribution Panels
3.3.1
Fuse Panels
Mechanical specifications of the fuse panels
The mechanical specifications of the fuse panels are listed in Table 6 below.
Figure 5
Front view of the 20 QFF 0-5 A fuse panels
The DC output connections are wire wrap or solder.
Table 6
Mechanical specifications of the fuse panels
Panel description
Figure
Height
Width
Weight
(20) QFF 0-5 A
60 A max
76.2 mm
(3.0 in.)
584 mm
(23.0 in.)
3 kg
(6.6 lb)
(16) QFF 0-5 A &
(12) ABS 5-30 A
300 A max
76.2 mm
(3.0 in.)
584 mm
(23.0 in.)
5 kg
(11.0 lb)
(16) QFF 0-5 A &
(6) TPN 5-30 A
250 A max
152.4 mm
(6.0 in.)
584 mm
(23.0 in.)
7 kg
(15.4 lb)
(8) TPN 5-30 A
250 A max
152.4 mm
(6.0 in.)
584 mm
(23.0 in.)
7 kg
(15.4 lb)
(4) RS100P 70-100 A
300 A max
152.4 mm
(6.0 in.)
584 mm
(23.0 in.)
8 kg
(17.8 lb)
(4) CRS200P 150-200 A
600 A max
228.6 mm
(9.0 in.)
584 mm
(23.0 in.)
22 kg
(48.4 lb)
(4) CRS200P 150-200 A
(w/load shunts)
600 A max
228.6 mm
(9.0 in.)
584 mm
(23.0 in.)
24 kg
(52.9 lb)
(4) TPL 225-600 A
1600 A max
304.8 mm
(12.0 in.)
584 mm
(23.0 in.)
32 kg
(70.4 lb)
(18) TPS 1-70 A
600 A max
178 mm
(7.0 in.)
584 mm
(23.0 in.)
35 kg
(77.0 lb)
Note 1: An alarm circuit pack with an alarm indication LED is standard on all panels
Note 2: (4) CRS200P 150-200 A (w/load shunts) is equipped with four shunts.
Table 7
Fuse sizes available for the (20) QFF 0-5 A fuse panels
Fuse type
Current (A)
CPC
QFF1A
1.333
A0205202
QFF1B
2
A0205203
QFF1C
3
A0205204
QFF1D
5
A0205205
QFF1E
0.18
A0205206
QFF1F
0.25
A0205207
QFF1G
0.5
A0205208
QFF1H
0.75
A0205209
QFF3A
DUMMY
A0205210
FA