• Install smoke alarms on sloped, peaked or cathedral

ceilings at or within 0.9 m (3') of the highest point
(measured horizontally). NFPA Standard 72 states: “Smoke
alarms in rooms with ceiling slopes greater than 0.3 m in
2.4 m (1' in 8') horizontally shall be located on the high
side of the room.” NFPA Standard 72 states: “A row of
detectors shall be spaced and located within 0.9 m (3') of
the peak of the ceiling measured horizontally” (Image 2B
and Image 2C).