beautypg.com

Warning, Piezoelectric igniter system, Replacing the manifold/burner assembly – Kenmore 153.331572 User Manual

Page 30: Explosion hazard

background image

30

control valve/thermostat. Finally, start the thermocouple nut
and turn it all the way in by hand. An additional quarter turn
with a 3/8” open-end wrench will then be sufficient to seat
the lockwasher. When you are finished, connect the two
wire leads that go to the thermal switch.

7. Reconnect the igniter wire.

8. Turn gas supply on and refer to the Lighting Instructions.

9. With the burner lit, check the gas control valve/thermostat

supply line, two piece wire connector, manifold tube,
and pilot tube connections for leaks. Check for leaks by
brushing on an approved noncorrosive leak detection
solution. Bubbles forming indicate a leak. Correct any leak
found. IMPORTANT: All leaks must be fixed immediately.

10. Replace the outer door.

DOOR GASKET

FLAME ARRESTOR

BRACKET

TIP

FIGURE 39.

MANIFOLD TUBE

TIP

BRACKET

SLOT

CLOSE-UP INSIDE VIEW OF

THE COMBUSTION CHAMBER.

FIGURE 40.

Piezoelectric Igniter System

The piezoelectric igniter system consists of the igniter button,
electrode, and wire. The pilot is ignited by an electric spark
generated when the igniter button is pressed. The spark gap
of 0.125 inch is set when the electrode is installed at the factory.
(Figure 41). Use only factory authorized piezoelectric igniter
parts for replacement.

SNAP-ON CONNECTOR

IGNITER
BUTTON

WIRE

TO

ELECTRODE

THERMOCOUPLE

PILOT

PILOT

BRACKET

ELECTRODE

TIP

.125” *

* NOTE: SPARK GAP DISTANCE MEASURED FROM ELECTRODE TIP TO PILOT.

FIGURE 41.

Replacing the Manifold/Burner Assembly

Explosion Hazard

• Tighten both manifold door screws securely.

• Remove any fiberglass between gasket

and combustion chamber.

• Replace viewport if glass is missing or

damaged.

• Replace two piece wire connector if missing or

removed.

• Replace door gasket if damaged.

• Failure to follow these instructions can result

in death, explosion, or fire.

WARNING

1. Check the door gasket for damage or imbedded debris

prior to installation.

2. Inspect the view port for damage and replace as required.

3. Insert the manifold/burner assembly into the burner

compartment, making sure that the tip of the manifold tube
engages in the slot of the bracket inside the combustion
chamber (Figures 39 & 40).

4. Inspect the door gasket and make sure there is no

fiberglass insulation between the gasket and the
combustion chamber.

5. Replace the two screws, which secure the manifold/

burner assembly door to the combustion chamber and
tighten securely. Once the manifold/burner assembly door
is tightened, visually inspect the door gasket between
the manifold/burner assembly door and the combustion
chamber for spaces or gaps that would prevent a seal.
IMPORTANT: Do not operate the water heater if the door
gasket does not create a seal between the manifold door
and the combustion chamber.

6. During the following procedure, do not cross-thread or

apply any thread sealant to any of the fittings listed below.
First, reconnect the manifold tubing to the gas control valve/
thermostat. NOTE: L.P. gas systems use reverse (left-hand)
threads on the manifold tube.

NOTE: If a ferrule nut needs to be installed for the pilot
tube, locate the one provided with your parts kit. Install it in
the gas control valve/thermostat at the pilot location, hand
tight only.

Next, insert the pilot tube into the ferrule nut until it bottoms
out. NOTE: Hold the tube in this position. Tighten the ferrule
nut with a wrench until the crimp connection seals to the
pilot tube. Continue to tighten until the nut is tight in the gas