Page 4

background image

The following diagram shows that the light intensity gradually decreases as the
viewing angle is increased. Use this information to determine the best location
for the strobe light.

2. APPLICATIONS

PRIMARY DIRECT AND INDIRECT VISIBLE SIGNAL

Locate the strobe light on the ceiling in the center of the room or on
the wall a minimum of 80"(2 m) above the floor.
For rooms larger than 250 sq. ft. (14 ft. by 16 ft. - 4.27m by 4.88 m) the
notification device should be located within 16 ft. (4.88m) of the pillow.

SUPPLEMENTARY VISIBLE SIGNAL

The strobe may be located less than 80" (2 m) above the floor.

3. RECOMMENDED LOCATIONS OF VISUAL SIGNALING DEVICES

• Locate the first strobe light in the bedroom in which the hearing impaired

individual sleeps. If the bedroom door is kept closed at night, an interconnect-
ing smoke detector must also be installed in that bedroom.

• Locate additional strobe lights in any lived-in room where a hearing impaired

individual would need to be notified of an alarm condition.

4. LOCATIONS TO AVOID

• In direct sunlight or high ambient light areas; the bright light may reduce ones

ability to notice the strobe light.

• In areas where the temperature may fall below 32˚F (4.4˚C) or rise above 100˚F

(37.8˚C).

• In areas with high humidity.

WALL

CEILING

25 90

25 85

30 80

30 75

35 70

35 65

40 60

45 55

55 50

75 30-45

90 5-25

100

0

(LIGHT INTENSITY)

(IN DEGREES)

PERCENT

ANGLE

90°

90°

90°

90°

45°

45°

45°

45°

SOURCE

LIGHT

SOURCE

LIGHT

WALL

CEILING

25 90

25 85

30 80

30 75

35 70

35 65

40 60

45 55

55 50

75 30-45

90 5-25

100

0

(LIGHT INTENSITY)

(IN DEGREES)

PERCENT

ANGLE

90°

90°

90°

90°

45°

45°

45°

45°

SOURCE

LIGHT

SOURCE

LIGHT

This manual is related to the following products: