AYXP7FR

3 – 14

Indoor/
outdoor
units in
complete
shutdown

2 times

2

-0

Cycle tempera-
ture

Compressor high-
temperature error

(1)

Check the outdoor unit air
outlet for blockage.

(1)

Ensure unobstructed
air flow from the out-
door unit air outlet.

(2)

Check if the power supply
voltage is 90 V or higher at
full power.

(2)

Connect power sup-
ply of proper voltage.

(3)

Check the pipe connec-
tions for refrigerant leaks.

(3)

Charge the specified
amount of refrigerant.

(4)

Measure resistance of the
outdoor unit compressor
thermistor.
(TH1: Approx. 53 k

Ω at

25

°C)

(4)

Replace the outdoor
unit compressor ther-
mistor assembly.

(5)

Check the expansion
valve for proper operation.

(5)

Replace the expan-
sion valve coil, expan-
sion valve or outdoor
unit control PWB
assembly.

Indoor
unit in
operation
Outdoor
unit in
tempo-
rary stop

-1

Temporary stop due
to compressor dis-
charge overheat *3

(Temporary stop for cycle pro-
tection)

-2

Temporary stop due
to outdoor unit heat
exchanger overheat
*3

(Temporary stop for cycle pro-
tection)

-3

Temporary stop due
to outdoor unit heat
exchanger overheat
*3

(Temporary stop for cycle pro-
tection)

-4

Temporary stop due
to 2-way valve
freeze *3

(Temporary stop for cycle pro-
tection)

Indoor
unit in
operation
Outdoor
unit in
tempo-
rary stop

3 times

3

-0

Dry operation

Temporary stop due
to dehumidifying
operation *3

(Temporary stop for cycle pro-
tection)

Indoor/
outdoor
units in
complete
shutdown

5 times

5

-0

Outdoor unit
thermistor
open-circuit

Heat exchanger
thermistor open-cir-
cuit error

(1)

Check connector CN8 of
the outdoor unit ther-
mistor for secure installa-
tion.

(1)

Correct the installa-
tion.

-1

Outside tempera-
ture thermistor
open-circuit error

(2)

Measure resistance of out-
door thermistors TH1 to
TH5.

(2)

Replace the outdoor
unit thermistor assem-
bly.

-2

Suction thermistor
open-circuit error

(3)

Check the lead wires of
thermistors TH1 through
TH5 on the outdoor unit
control PWB for open-cir-
cuit.

(3)

Replace the outdoor
unit thermistor assem-
bly.

-3

2-way valve ther-
mistor open-circuit
error

(4)

No abnormality found in
above inspections (1)
through (3).

(5)

Replace the outdoor
unit control PWB
assembly.

-4

Discharge ther-
mistor open-circuit
error

Status of

indoor/

outdoor

units

Indication

by LED1

on out-

door unit

*2

Malfunction

No. dis-

played on

main unit

display sec-

tion *1

Content of diagnosis

Inspection location/method

Remedy

Main
cate-

gory

Sub-

cate-

gory

Main category

Sub-category

This manual is related to the following products: