Installation site selection – Sanyo CM1972 User Manual

Page 66

background image

4

1-5. Additional Materials Required for Installation

1.

Refrigeration (armored) tape

2.

Insulated staples or clamps for connecting wire

(See local codes)

3.

Putty

4.

Refrigeration lubricant

5.

Clamps or saddles to secure refrigerant tubing

2. Installation Site Selection

2-1. Indoor Unit

AVOID:

direct sunlight.

nearby heat sources that may affect performance of the

unit.

areas where leakage of flammable gas may be expected.

placing or allowing any obstructions near the A/C inlet or

outlet.

installing in rooms that contain instant-on (rapid-start)

fluorescent lamps. (These may prevent the A/C from

receiving signals.)

places where large amounts of oil mist exist.

installing in locations where there are devices that

generate high-frequency emissions.

DO:

select an appropriate position from which every corner of

the room can be uniformly cooled. (High on a wall is best.)

select a location that will hold the weight of the unit.

select a location where tubing and drain hose have the

shortest run to the outside. (Fig. 1)

allow room for operation and maintenance as well as

unrestricted air flow around the unit. (Fig. 2)

install the unit within the maximum elevation difference

(H1, H2, H3, H4) above or below the outdoor unit and

within a total tubing length (L1+L2+L3, L1+L2+L3+L4)

from the outdoor unit as detailed in Table 3 and Fig. 3a.

Drain hose

Indoor unit

Outside drainage

Fig. 1

2" (5 cm)

min.

6" (15 cm)
min.

Front View

2" (5 cm)

min.

Fig. 2

INDOOR
UNIT (1)

INDOOR
UNIT (4)

INDOOR
UNIT (3)

INDOOR
UNIT (2)

Tubing length (L1)

L2

L3

L4

H2

H3

H4

OUTDOOR
UNIT

Elevation
difference (H1)

Fig. 3a

WARNING

To prevent abnormal heat generation

and the possibility of fire, do not

place obstacles, enclosures and

grilles in front of or surrounding the

air conditioner in a way that may

block air flow.

Indoor unit

Floor level

Wall

Minimum height
from floor level

5' (1.5 m)

Fig. 3b

For stable operation of the

air conditioner, do not

install wall-mounted type

indoor units less than 5'

(1.5 m) from floor level.

CAUTION

07-156 CM-CLM1972-3172 6/6/07 9:35 AM Page 4