Siemens SQM5 User Manual
Page 28
Technical Instructions
SQM5… Reversing Actuators
Document No. 155-517P25
July 9, 2007
Page 28
Siemens Building Technologies, Inc.
Specifications,
continued
AGA56.43A…
AGA56.9A
ASZ... Potentiometers
AGA56.43A… Electronic circuit boards
Same specifications as AGA56.41A
except:
Input signal
0 to 10 Vdc
Impedance
Voltage
input
≥100K Ω
AGA56.9A… Multi function electronic Single
potentiometer
circuit boards
ASZ... (1000 ohm) is required
Operating voltage
24 Vac +10%-15%
110 Vac -15% to 120 Vac +10%
220 Vac -15% to 240 Vac +10%
Operating frequency
50 to 60 Hz
Input signals
4 to 20 mA
0 to 20 mA
0 to 10 Vdc
0 to 135 ohm
Impedance
Current
input
≤300 Ω
Voltage
input
≥100K Ω
Output signals
4 to 20 mA
0 to 20 mA
0 to 10 Vdc
Max output load
Current output
<600 ohm
Voltage output
> 1.5K ohm
Zero adjustment
MIN: 0 to 75%
Span adjustment
MAX: min-100%
Split ranging (SHIFT)
4 to 20 mA on terminal ZF
Input signal override (POS)
Line voltage (... Vac) on terminal P
adjust with POS potentiometer
Ambient operating temperature
-5°F to 140°F (-20°C to 60°C)
Shipping temperature
-58°F to 140°F (-50°C to 60°C)
Auto/manual switch
2-position switch
Manual toggle switch
3-position switch
Weight
0.7 lb (0.33 kg)
ASZ... Potentiometers
Versions
Single and double potentiometer
Resistor values
See Table 2 and Data Sheet 7921.
Hysteresis
< 0.3% related to drive shaft