Technical Instructions

SQM5… Reversing Actuators

Document No. 155-517P25
July 9, 2007

Page 26

Siemens Building Technologies, Inc.

Specifications

SQM5... Reversing
Actuator

SQM5... Reversing actuator
Agency approvals

UL, CSA, CE

Operating voltage

24 Vac +10%-15%

110 Vac-15% to 120 Vac +10%

220 Vac-15% to 240 Vac +10%

Operating frequency

50 to 60 Hz

Power consumption

20 VA

Type of motor

Reversing synchronous motor

Duty cycle

100%

Torque

See Table 1.

Maximum shaft torque

AGA58.1

90

lb-in

AGA58.2

200

lb-in

AGA58.3

220

lb-in

AGA58.4

270

lb-in

AGA58.7

400

lb-in

Timings

See Table 1.

Rotational range of operation

SQM5x.xxxxxA models

0° to 160°

SQM5x.xxxxxx3 models

0° to 90°

SQM5x.xxxxxx4 models

0° to 135°

SQMSx.xxxxxx6 models

0° to 160°

Direction of rotation

Reversible

Shaft

Selectable. See Table 2.

Custom versions on request

Shaft disengagement

Independent, cam and drive shaft

Number of auxiliary switches

4 switches (standard, maximum 6)

Limit switches

2 switches (standard)

Electrical rating of auxiliary switches

7.5 (3) A, 250 Vac

Mounting position

Optional

Ambient operating temperature

-5°F to 140°F (-20°C to 60°C)

Shipping temperature

-58°F to 140°F (-50°C to 60°C)

NEMA ratings

NEMA 1, 2, 3, 3R, 3S, 5, 12, and 13

Connections
Switches

Spade

connectors

Boards

Screwed and spade connectors

Dimensions

See Figures 28 through 31.

Weight

7.3 lb (3.3 kg)

Housing

Aluminum pressure die casting

Enclosure (cover)

Lexan

Motor

Lock

resistant

Disengagements

Manual for drive and cam shaft