Siemens SQM5 User Manual
Page 26
Technical Instructions
SQM5… Reversing Actuators
Document No. 155-517P25
July 9, 2007
Page 26
Siemens Building Technologies, Inc.
Specifications
SQM5... Reversing
Actuator
SQM5... Reversing actuator
Agency approvals
UL, CSA, CE
Operating voltage
24 Vac +10%-15%
110 Vac-15% to 120 Vac +10%
220 Vac-15% to 240 Vac +10%
Operating frequency
50 to 60 Hz
Power consumption
20 VA
Type of motor
Reversing synchronous motor
Duty cycle
100%
Torque
See Table 1.
Maximum shaft torque
AGA58.1
90
lb-in
AGA58.2
200
lb-in
AGA58.3
220
lb-in
AGA58.4
270
lb-in
AGA58.7
400
lb-in
Timings
See Table 1.
Rotational range of operation
SQM5x.xxxxxA models
0° to 160°
SQM5x.xxxxxx3 models
0° to 90°
SQM5x.xxxxxx4 models
0° to 135°
SQMSx.xxxxxx6 models
0° to 160°
Direction of rotation
Reversible
Shaft
Selectable. See Table 2.
Custom versions on request
Shaft disengagement
Independent, cam and drive shaft
Number of auxiliary switches
4 switches (standard, maximum 6)
Limit switches
2 switches (standard)
Electrical rating of auxiliary switches
7.5 (3) A, 250 Vac
Mounting position
Optional
Ambient operating temperature
-5°F to 140°F (-20°C to 60°C)
Shipping temperature
-58°F to 140°F (-50°C to 60°C)
NEMA ratings
NEMA 1, 2, 3, 3R, 3S, 5, 12, and 13
Connections
Switches
Spade
connectors
Boards
Screwed and spade connectors
Dimensions
See Figures 28 through 31.
Weight
7.3 lb (3.3 kg)
Housing
Aluminum pressure die casting
Enclosure (cover)
Lexan
Motor
Lock
resistant
Disengagements
Manual for drive and cam shaft