Siemens SQM5 User Manual
Page 22
Technical Instructions
SQM5… Reversing Actuators
Document No. 155-517P25
July 9, 2007
Page 22
Siemens Building Technologies, Inc.
AGA56.41/42/43
Circuit Board
Installation, Continued
8. Make the following connections to the
actuator: See Figure 22.
a. Connect the wire, marked “1” from
the circuit board to switch I,
terminal 1.
b. Connect the wire, marked “2” from
the circuit board to switch II,
terminal 2.
c. Connect the wire, marked “3” from
the circuit board to switch III,
terminal 3.
d. Connect the wire, marked “13”
from the circuit board to switch III,
terminal 13.
e. Connect the blue neutral wire
marked “N” to the double terminal
block located on the outer end of
the switch housing
f.
Connect the grounding wire
marked "51" to the ground terminal
located to the right of the
auto/manual switch.
EA0577R2
2
51
N
13
3
1
0
MAN.
AUTO
I
11
21
1
2
22
12
II
3
23
13
III
4
24
14
IV
5
25
15
V
6
26
16
VI
7
27
17
VII
8
28
18
VIII
TERMINAL
BLOCK
N
Figure 22.
AGA56.9A…
Circuit Board
Installation
1. Remove the ASZ... potentiometer if
already installed on the SQM5...
actuator. See Potentiometer
Removal/Installation Instructions.
2. Remove the AGA56.9A… circuit
boards from the packaging. The three
separate AGA56.9A circuit boards are
shipped in a circuit board mounting
bracket.
3. Remove the two upright circuit boards
from the mounting bracket by gently
pulling aside the vertical supports and
sliding the boards upward. Remove
the base circuit board from the bottom
of the mounting bracket. Discard the
shipping mounting bracket.