Technical Instructions

SQM5… Reversing Actuators

Document No. 155-517P25
July 9, 2007

Page 10

Siemens Building Technologies, Inc.

Wiring Connections

NOTE: SQM5… actuators require a single source, single phase power supply.

Wiring connections vary depending on which AGA56…. circuit board is installed.

AGA56.1… circuit boards.

See Figures 7 and 8.

Manual Operation

1.

Set the AUTO/MAN switch in the MAN position.

2.

Connect ground to the screw located below the shaft release button.

3.

Connect neutral to the double terminal block, located on the left side of the gray
switch housing.

4.

Only terminal "L" must be to enable manual operation. The actuator can now be
driven to the maximum position (switch cam I) or the fully closed "economy
position" (switch cam II) by using the toggle switch located to the left of the
AUTO/MAN switch.

Automatic Operation

1. Set the AUTO/MAN switch in the AUTO position.

2. Connect ground to the screw located below the shaft release button.

3. Connect neutral to the double terminal block located on the left side of the gray

switch housing.

4. Connect line voltage to terminal A to drive the actuator in the opening direction.

5. Connect line voltage to terminal Z to drive the actuator in the closing direction.

CAUTION:

Do not power terminals A and Z simultaneously. Actuator damage will occur.

EA0555R3

AGA56.1A97

MAN

AUTO

1

2

11

21

M

I

II

III

IV

V

12

22

13

23

14

15

24

25

3

4

5

"Economy"/Fully closed
Minimum/Low fire

Maximum/High fire

Auxilliary

IV...VI

III

II

I

1

2

13

21 12

N

VI

16

26

6

51

A

actuator switch

wire leads

L

Z

shown in
auto position

ASZ...

(1000 Ohm)

b

a

c

Figure 7. Basic Functional Diagram of AGA56.1…