Specification, Environment – Sierra Monitor Corporation ZSE30 User Manual
Page 9
ZSE30
ISE30
Rated Pressure Range
-100 to 100 kPa
0 to 1 MPa
Set Pressure Range
-101 to 101 kPa
-0.1 to 1 MPa
Withstand Pressure
500 kPa
1.5 MPa
Setting and Display Resolution
0.2 kPa
0.001 MPa
Fluids
Air, inert gases and incombustible gases
Power Supply Voltage
12 to 24V DC,
±10%,ripple (p-p) 10% or less(Protected against inverse connection)
Current Consumption
45mA or less (No load)
Switch Output
Note 1)
NPN or PNP open collector output .1 output
Max. Load Current
80mA
Max. Impressed Voltage
30V (During NPN output)
Residual voltage
1V or less (@80mA load current)
Response Time
2.5ms or less (chattering-proof function working :20,160,640 or 1280ms selectable)
Short Circuit Protection
Provided
Repeatability
±0.2%F.S. ±2 digits or less
±0.2%F.S.±1 digit or less
Voltage Output
Note 2)
Output Voltage : 1 to 5V
±2.5%F.S. or less (within rated pressure range)
Linearity :
±1%F.S. or less, Output impedance : Approx. 1kΩ
Analog
Output Current Output
Note 3)
Output Current : 4 to 20mA
±2.5%F.S. or less (within rated pressure range)
Linearity :
±1%F.S. or less
Max. Load Impedance : 300
Ω (@12VDC), 600Ω (@24VDC) Min. Load Impedance : 50Ω
Hysteresis Mode
Hyster
esis
Window Comparator
Mode
Variable(from 0)
Display Method
3.5 digits 7-segment display, dual-color display(red/green) Sampling rate:5 times/1 sec
Indicator Accuracy
±2%F.S. ±2 digits (@25±3°C)
±2%F.S. ±1 digit (@25±3°C)
Indicator Lamp
Lit when ON (Green)
Temperature Characteristic
±2%F.S. or less (@25°C reference)
Enclosure IP40
Ambient Temperature
Operation : 0 to 50
°C, Storage : -10 to 60°C (No condensation or no freezing)
Ambient Humidity
Operation
⋅Storage : 35 to 85%RH (No condensation)
Withstand Voltage
1000VAC,1 minute (between lead block and case)
Insulation Resistance
50M
Ω or more @500VDC M (between lead block and case)
Vibration proof
10 to 150 Hz, 1.5mm double amplitude, 2 hours each in directions of X, Y and Z respectively
Impact proof
100m/s
2
, 3 times each in directions of X, Y and Z respectively
Standard
CE marking, UL/CSA(E216656)
Note 1) Analog output cannot be selected when switch output is selected.
Note 2) Both switch output and current output cannot be selected simultaneously when voltage output is
selected.
Note 3) Both switch output and voltage output cannot be selected simultaneously when current output is
selected.
Piping specification
Model
01
T1
C4H
C6H
N7H
C4L
C6L
N7L
Port size
R1/8
M5
×0.8
NPT1/8
M5
×0.8
−
−
−
−
−
−
One-touch fitting
straight type
−
−
φ4mm
φ5/32inch φ6mm φ1/4inch
−
−
−
One-touch fitting
elbow type
−
−
−
−
−
φ4mm
φ5/32inch φ6mm φ1/4inch
Sensor pressure sensing part: silicone, Pipe port: C3602 (electroless nickel plating),
Material
O-ring: HNBR
O-ring: NBR
O-ring: NBR, Fitting: PBT
Lead wires with
connector included
(2m)
81g 76g
78g
Mass
(Weight)
Lead wires with
connector not included
43g 38g
40g
Environment
-8-
PS##-OMF0010-C
Specification