7design and principle of operation – Samson Electri Actuator Type 3374 EB 8331-1 EN User Manual
Page 7

EB 8331-1 EN
7
Design and principle of operation
Digital positioner
1)
Operating mode 1
Operating mode 2
Operating mode 3
Input signal
2)
Range
4...20 mA, Ri = 0.05 k
W
2...10 V, Ri = 10 k
W
0...20 mA, Ri = 0.05 k
W
0...10 V, Ri = 10 k
W
As per settings
3)
Resolution
10 Bit
Position feedback
signal
4)
Range
4...20 mA, R
B
0.2
£
k
W
2...10 V, R
B
³
5 k
W
0...20 mA, R
B
£
0.2 k
W
0...10 V, R
B
³
5 k
W
As per settings
3)
Resolution
8 Bit
Characteristic
Increasing, actuator stem retracts or extends
as the input signal increases
As per settings
3)
Travel
Adjustable
6 to 19 mm at 15 mm rated travel
6 to 35 mm at 30 mm rated travel
Setting
Using travel calibration button
(1 mm each time the button is pressed)
As per settings
3)
using button
1 binary input
Electrically isolated, switching voltage 18 to 30 V DC, approx. 7 mA
1 binary output
Electrically isolated semiconductor contact, max. 45 V DC,
min. 3 V DC, max. 25 mA
Integrated interface for SAMSON
memory pen/PC
Data transmission including settings, operating status and alarms
Transfer protocol: SAMSON SSP protocol
Total delay time
Approx. 30 ms
Accuracy
£
2.5 %
without taking the dead band into account
1)
Maximum two current inputs may be switched in series
2)
Maximum values ±50 mA or ±25 V
3)
SAMSON TROVIS-VIEW Operator Interface software, SAMSON memory pen