· RS485 Wiring

Solar Inverters NT 10000 can be cross-lin-

ked via RS485. When doing so, please keep

in mind that the Solar Inverters must be

connected in series. Cross-linking them

point-to-point is not admissible. Interface

RS485 is connected via the printed circuit

board terminals and the corresponding

M12 cable glands inside the housing. Prior

to wiring the RS485, move the cover of the

Solar Inverter up, and fix it in position by

tightening a lateral screw. See chapter 2.1

«Safety Instructions».

The required cable terminal block («X6»)

with the connections «RS485 +», «RS485 -»,

and «RS485 GND» is in the lower section of

the circuit board (see illustr. page 115).

Caution: There are two each of all termi-

nals, so the ingoing and outgoing lines can

be connected separately.

Use a twisted two-wire cable for the RS485

wiring of the Solar Inverter. Connect the

terminals «RS485 +» between the Solar

Inverters with one core and the terminals

«RS485 -» with the other.

If you use a shielded twisted two-wire

cable, you can earth the shield. That will

improve the communication reliability.

With the last Solar Inverter, the jumper

«RS485 MATCH» must be closed. With all

other Solar Inverters, it has to be in the

open position (see chapter 3.6 «Com-

munication Link»).

· Connecting a cable to the spring-loaded

terminal

· Use a small screwdriver. Press the orange

terminal. The terminal will open.

· Insert the (at least 11 mm bare) cable into

the respective terminal hole.

· Release the pressure from the screw-

driver. The cable is now attached to the

connection.

· Make sure the cable is connected tightly.