Installation site requirements – Sunway NT 10000 User Manual

Page 23

background image

If the Solar Inverter is installed in a switch

cabinet, make sure the heat is removed to

a sufficient degree.

The ambient temperature may not drop

below -25° C or rise above +40° C.

To protect the Solar Inverter from unneces-

sary external heat sources, do not expose

the Solar Inverter to direct sunlight.

· Protection from Moisture and Foreign

Objects

Thanks to the high protection level IP 54,

the Solar Inverter can be installed indoors as

well as in a sheltered outdoor area, but it

may not be directly exposed to rain.

Make sure the dust filter on the lower left

side is not clogged by contamination.

That would impair the intake of cooling air.

Depending on the surroundings, the filter

should be cleaned at regular intervals.

Installation Site Requirements

· Mechanical Load-Bearing Capacity

During assembly, please keep in mind that

the Solar Inverter weighs 30 kg. The

assembly foundation must be solid and

capable of bearing the weight in the long

run.

· Thermal Interaction

The assembly foundation must be made

of flame-retardant material (unsuitable:

wooden or plastic foundation; suitable:

concrete and masonry), because the frame

of the Solar Inverter can reach up to 70° C.

Maintain a minimum distance of 300 mm

to other devices, cabinets, ceilings, cable

channels, etc. above, below, and next to

the housing.

The Solar Inverter must be installed in an

upright position to ensure unobstructed

convection.

Do not install several Solar Inverters on

top of each other, as they might heat

each other up.