The graphic display shall assist the user by providing step by step help in the
user's language.
o
LED mimic diagram
o
The mimic diagram shall enable display of installation parameters, configuration,
operating status and alarms and indication of operator instructions for switching
operations (e.g. bypass).
o
It shall be possible to display the following measurements:
inverter output phase-to-phase voltages;
inverter output currents;
inverter output frequency;
voltage across battery bank;
battery charge or discharge current;
rectifier/charger
input phase-to-phase voltages;
rectifier/charger input currents;
active and apparent power;
power factor of the load;
battery
temperature.
display of status conditions and events
o
It shall be possible to display the following indications:
load on battery power;
load on UPS;
load on automatic bypass;
general
alarm;
battery
fault;
remaining battery backup time;
low battery warning;
bypass AC source outside tolerances;
o
Additional information shall be provided in view of accelerating servicing of the
system.
o
Log of time-stamped events
This function shall store in memory and make available, for automatic or
manually initiated recall, time-stamped logs of all important status
changes, faults and malfunctions, complete with an analysis and display
of troubleshooting procedures. It shall be possible to time stamp and
store at least 2 000 events.
B. Front Panel LCD Display: The UPS control panel shall provide a back-lit, color graphic
display with choice of over 15 operating languages for indication of UPS status, metering,
battery status, alarm/event log, and advanced operational features. The display provides
access to:
Mimic diagram indicating UPS power flow
Measurements, status indications and events
Personalization menu protected by a password, used to make specific settings
Event log with time stamping
Access to all measurements
System Parameters Monitored: The visual display will display the following system
parameters based on true RMS metering:
Measurements:
Input voltage (Ph-Ph)
Input current per phase
APC – MGE Galaxy 5000 Specification (60Hz)
8
Effective: June 1, 2008 REV X0 JJG
Parallel Module