Schneider Electric MGE GALAXY 5000 User Manual
Page 3
UPS Module Operating:
0° to 40°C (32°F to 104°F)
Non-Operating:
-20° to +45°C (-4°F to 113°F)
B. Relative humidity (operating and storage): 0 to 95% non-condensing
C. Barometric Pressure:
Up to 1000 meters above sea level (up to 2000 meters with
ambient temperature less than 28°C) / (up to 12,000 meters above sea level non operating)
D. Audible Noise:
69 dBA at 3 feet
1.8 WARRANTY
A. UPS Module: The UPS shall be covered by a full parts and labor warranty from the
manufacturer for a period of twelve (12) months from date of installation or acceptance by
customer or eighteen (18) months from date of shipment from the manufacturer, whichever
occurs first.
B. Battery: The battery manufacturer’s warranty shall be passed through to the final customer and
shall have a minimum period of one year.
1.9
SERVICE AND SPARE PARTS
The manufacturer shall, upon request, provide spare parts kits for the UPS module in a timely
manner as well as provide access to qualified factory trained first party service personnel to provide
preventative maintenance and service on the UPS module when required.
1.10
MAINTENANCE, ACCESSIBILITY AND SELF DIAGNOSTICS
All UPS subassemblies, as well as the battery, shall be accessible from the front. UPS design
shall provide maximum reliability and minimum MTTR (mean time to repair). To that end, the
UPS shall be equipped with a self-test function to verify correct system operation. The self-test
function shall identify the subassembly requiring repair in the event of a fault. The electronic UPS
control and monitoring assembly shall therefore be fully microprocessor based, thus doing away
with all potentiometer settings. This shall allow:
Auto-compensation of component drift;
Self-adjustment of replaced subassemblies;
Extensive acquisition of information vital for computer-aided diagnostics (local or remote);
Socket connection to interface with computer-aided diagnostics system.
The UPS shall be repairable by replacing standard subassemblies requiring no adjustments.
Communication via a modem with a remote maintenance system shall be possible.
2.0 PRODUCT DESCRIPTION
2.1
APPROVED MANUFACTURERS & PRODUCT DESCRIPTION
A. Approved Manufacturer(s): The specified equipment will be manufactured by APC by
Schneider Electric or approved manufacturer in compliance with specifications.
APC – MGE Galaxy 5000 Specification (60Hz)
3
Effective: June 1, 2008 REV X0 JJG
Parallel Module
B. Product Description: This specification describes a three-phase, double conversion, on-line,
solid state Uninterruptible Power System, hereafter referred to as the UPS. The UPS shall
operate in conjunction with the existing building electrical system to provide power conditioning,
back-up power protection and distribution for electronic equipment loads. The system shall
consist of a solid state IGBT PWM inverter, IGBT rectifier with a power factor corrected input,