2.2 D-2

BATTERY DC CURRENT

40

KVA

50

KVA

60

KVA

80 KVA

100 KVA

130 KVA

ADC

At Max End

Voltage

109 137 164 219

273

355

3.1 C

WEIGHTS AND DIMENSIONS

Dimensions (Inches)/ WEIGHT (Lbs.)

KVA

UPS

40 to

80kVA

UPS

100 to

130kVA

TOP

Entry

Battery

Height

75.0 75.0 75.0 75.0

Width

28.0 28.0 14.0

28/36/48

Depth

33.4 33.4 33.4 33.4

Weight

904 1168

Consult drawing

Consult drawing

(stand-alone

dimensions)

3.1 D

UPS MODULE HEAT REJECTION



BTU/HR

40 kVA

9250

50 kVA

11560

60 kVA

13870

80 kVA

18500

100 kVA

19610

130 kVA

25490














APC – MGE Galaxy 5000 Specification (60Hz)