48
9-2-3. Only outdoor unit does not run
A. Check setting temperature.
B. Check power relay in outdoor unit.
Outdoor unit still does
not run.
NO
Try to run with another remote
control unit.
•
OK
Remote control unit is defective.
Try to lower setting temperature by
temperature setting button ( button).
Is room temperature too low?
Measure coil resistance of power
relay. (PR)
•
Check indoor PCB Ass’y.
•
OK
099-464 SM (17-56) 2/7/00 4:19 PM Page 48
See also other documents in the category Sanyo Conditioners:
- ECO-i WCHDZ20053 (2 pages)
- CL0951 (3 pages)
- ECO G SPW-GU075XH (9 pages)
- CM1972 (99 pages)
- CR365GX56 (1 page)
- 42XS32A (3 pages)
- CL2432A (3 pages)
- 9 (2 pages)
- KH3072R / C3072R (180 pages)
- CH0971 (2 pages)
- 26UW72R (2 pages)
- C2432 (17 pages)
- CR1304GDZH8 (1 page)
- KH2672R (48 pages)
- ECOi C0905DXHN8 (10 pages)
- CH1251 (98 pages)
- 30KS32A (3 pages)
- Concealed Duct & Heat Pump H 13.9-14.9 SEER (2 pages)
- 42TLS32A (3 pages)
- CL2462R (58 pages)
- C1251 (83 pages)
- DHX3652 (114 pages)
- 42XHW72R (2 pages)
- 09KS71 (2 pages)
- C3632A (3 pages)
- 18KS72 (2 pages)
- 12XS71 (2 pages)
- ECO R410A (48 pages)
- KS2472 (117 pages)
- INVERTER SPLIT SYSTEM 8.53E+13 (24 pages)
- C3082 (104 pages)
- KHHS2672R (4 pages)
- CHX06052 (246 pages)
- CL1211 (16 pages)
- CH3082 (109 pages)
- Indoor Unit thx1852 (4 pages)
- 42TW72R (2 pages)
- KHS1872 (111 pages)
- C4232 (66 pages)
- CHDZ14053 (265 pages)
- CL0971 (4 pages)
- CHDX14053 (243 pages)
- 09KS51 (3 pages)
- 12RLS11 (3 pages)