John Deere PR-G7500M User Manual
Page 18

18
Operator’s Manual
CONTROLS
CABLE SIZE:
Equipment damage can result from low voltage. Therefore, to prevent
excessive voltage drop between the generator and the equipment,
the cable should be of adequate gauge for the length used. The cable
selection chart gives the maximum cable lengths for various gauges of
wire which can adequately carry the loads shown.
ELECTRIC MOTOR LOADS:
It is characteristic of common electric motors in normal operation to
draw up to six times their running current while starting. This table
may be used to estimate the watts required to start “CODE G” electric
motors.
CAUTION: IF AN ELECTRIC MOTOR FAILS TO START OR
REACH RUNNING SPEED, TURN OFF THE APPLIANCE OR
TOOL IMMEDIATELY TO AVOID EQUIPMENT DAMAGE.
ALWAYS CHECK THE REQUIREMENTS OF THE TOOL OR
APPLIANCE BEING USED COMPARED TO THE RATED
OUTPUT OF THE GENERATOR.
OPERATING THE GENERATOR
CURRENT LOAD IN WATTS MAXIMUM CABLE LENGTH (FEET)
IN AMPS 120 VOLTS 240 VOLTS #8 WIRE #10 WIRE #12 WIRE #14 WIRE
#16 WIRE
2.5 300 600 1000 600
375
250
5 600 1200 500 300
200
125
7.5 900 1800 350 200
125
100
10 1200 2400 250 150
100
50
15 1800 3600 150 100
65
20 2400 4800 175 125 75
50
25 3000 6000 150 100 60
30 3600 7200 125 65
40 4800 9600 90
WATTS REQUIRED TO START MOTOR
MOTOR (H.P.) RUNNING WATTS REPULSION INDUCTION CAPACITOR
SPLIT PHASE
1/8
275
600
850
1200
1/6
275
600
850
2050
1/4
400
850
1050
2400
1/3
450
975
1350
2700
1/2
600
1300
1800
3600
3/4
850
1900
2600
1
1100
2500
3300