Specifications, 1 general specifications – MITSUBISHI ELECTRIC QA6ADP User Manual
Page 8

7
3. SPECIFICATIONS
 
3.1 General Specifications 
This section describes general specifications of the QA6ADP. 
Item Specifications
Operating ambient 
temperature 
0 to 55
Storage ambient 
temperature 
-20 to 75
Operating ambient 
humidity 
10 to 90 % RH, No-condensing
Storage ambient 
humidity 
10 to 90 % RH, No-condensing
Frequency
Accelera
-tion
Amplitude
Sweep
count
10 to 57 Hz
----
0.075 mm
Under 
intermittent 
vibration 
57 to 150 Hz 9.8 m/s
2
----
10 to 57 Hz
----
00.35 mm
(0.001 in.)
Vibration 
resistance 
Conforming
to
JIS B 3502,
IEC 61131-2 Under
continuous 
vibration 
57 to 150 Hz 4.9 m/s
2
----
10 times
each in
X, Y, Z
directions
(for 80
min).
Shock resistance
Conforming to JIS B 3502, IEC 61131-2
(147 m/s
2
, 3 times in each of 3 directions XYZ)
Operation 
ambiance 
No corrosive gasses
Operating 
elevation *3 
2000 m (6562 ft.) or less
Installation 
location 
Control panel
Overvoltage 
category *1 
II max.
Pollution degree *2
2 max.
Equipment 
category 
Class I
*1: This indicates the section of the power supply to which the equipment is assumed
to be connected between the public electrical power distribution network and the 
machinery within premises. 
Category II applies to equipment for which electrical power is supplied from fixed 
facilities. 
The surge voltage withstand level for up to the rated voltage of 300 V is 2500 V. 
*2: This index indicates the degree to which conductive material is generated in terms
of the environment in which the equipment is used. 
Pollution level 2 is when only non-conductive pollution occurs. A temporary 
conductivity caused by condensing must be expected occasionally. 
*3: Do not use or store the PLC in the environment when the pressure is higher than
the atmospheric pressure at sea level. 
Otherwise, malfunction may result. 
To use the PLC in high-pressure environment, please contact your local Mitsubishi 
Repress entative. 