MGE UPS Systems EPS 7000 User Manual
Page 24
1.5.3 Hidden Panel Indicators
The hidden panel is located behind the hinged cover, at the lowest pane of the front panel, refer to Figure 1-8.
The hidden panel includes the alphanumeric display and controls, and following controls and indicators, see Figure 1-
11.
Figure 1-11: Hidden Panel Alphanumeric LEDs and Pushbutton Indicators and Controls.
Hidden panel alphanumeric legend: (upper display, details on following page)
A
Emergency Shutdown
G
Battery charging
L
Overload
B
Rectifier/Charger on
H
Inverter fault
M
Bypass outside tolerance
C
Rectifier/Charger fault
I
Battery discharged
N
Maintenance position
D
Input Outside Tolerance
J
Inverter Desynchronized
F
Battery temp. outside Tolerance
K
Transfer Fault
(lower display)
(port) Test connector
fault Clear faults
(audio)
Alarm reset
1
Battery charge cycle
2
Return to float voltage
(key)
Security
3
Inverter sync/desync
4
Forced Transfer
5
Forced Shutdown
1.5.3.1 LED Alphanumeric Indicators
Fourteen alphabetically labeled LEDs provide detailed information on UPS status as follows:
A: Emergency shutdown
This red LED indicates that the emergency power off (EPO) or remote emergency power off (REPO) has been
activated. See section 2.10.1, Emergency power off.
B: Rectifier/charger on
This green LED indicates that the rectifier/battery charger is on.
Introduction
EPS 7000 Shared Systems
page 1 — 14
N
M
L
K
J
I
H
G
F
E
D
C
B
A
1
2
3
4
5
fault