DCA-10SPX3 A.C. GENERATOR — PARTS & OPERATION MANUAL — REV. #2 (01/17/11) — PAGE 37

DCA-10SPX3 — GENERATOR SHUT-DOWN PROCEDURE

10. The battery voltage gauge (Figure 26) will indicate the

voltage of the battery when the generator is operating.
Under normal operating conditions this voltage is
between 11.2 and 15.2 volts.

Figure 26. Battery Voltage Gauge

11. If there are no abnormal problems shown on the MPEC

LED display, turn both the MAIN and GFCI circuit
breakers to their ON position (Figure 27).

CIRCUIT BREAKER

GFI RECEPTACLE

CIRCUIT BREAKER

MAIN

ON

ON

12. Observe at the generator's ammeter (Figure 28) and

verify that it reads the anticipated amount of current
with respect to the load. The ammeter will only display a
current reading if the load is in use.

13. The generator will run until manually stopped or an

abnormal condition occurs.

Figure 27. Main and GFCI Circuit Breakers

Figure 28. Ammeter (Load)

A

0

40

60

75

20

Engine Shutdown
To shutdown the generator use the following procedure:

1. Place both the MAIN and GFCI circuit breakers to the

"OFF position" (Figure 29).

CIRCUIT BREAKER

MAIN

GFCI RECEPTACLE

CIRCUIT BREAKER

OFF

OFF

2. Let the engine cool by running 3-5 minutes with no load

applied.

3. Turn the key to the 'STOP' position to shut down the

engine (Figure 30).

Figure 30. Ignition Switch (OFF)

Figure 29. GFCI and Main Circuit Breaker

(OFF)