MGE UPS Systems EX-7 User Manual
Page 65

Installation and User Manual
Table 5-3: Battery Recharge time to recover 90% of the rated backup time after discharge at full load.
Configuration for
Configuration for
Configuration for
2 hours backup time
4 hours backup time
8 hours backup time
EX 5RT
7 hours
15 hours
24 hours
EX 7RT
5 hours
12 hours
20 hours
EX 11RT
7 hours
15 hours
24 hours
Table 5-4: Efficiency online (RL load) and batteries fully charged.
Table 5-5: Efficiency online (RCD load) and batteries fully charged.
Table 5-6: Efficiency on battery (RCD load).
kVA / kW
25%
50%
75%
100%
Output load percentage
5kVA /
4kWatts
87
87
89
88
89
89
88
88
Output: 220 / 230 / 240 Volts
Output: 200 / 208 / 250 Volts
7kVA /
4.9kWatts
87
87
89
88
89
89
88
88
Output: 220 / 230 / 240 Volts
Output: 200 / 208 / 250 Volts
11kVA /
8kWatts
89
88
90
90
89
89
87
88
Output: 220 / 230 / 240 Volts
Output: 200 / 208 / 250 Volts
kVA / kW
25%
50%
75%
100%
Output load percentage
5kVA /
4kWatts
90
89
91
91
91
91
92
91
Output: 220 / 230 / 240 Volts
Output: 200 / 208 / 250 Volts
7kVA /
4.9kWatts
90
89
91
91
91
91
92
91
Output: 220 / 230 / 240 Volts
Output: 200 / 208 / 250 Volts
11kVA /
8kWatts
90
89
92
91
91
90
91
90
Output: 220 / 230 / 240 Volts
Output: 200 / 208 / 250 Volts
kVA / kW
25%
50%
75%
100%
Output load percentage
5kVA /
4kWatts
90
89
91
90
91
91
91
91
Output: 220 / 230 / 240 Volts
Output: 200 / 208 / 250 Volts
7kVA /
4.9kWatts
90
89
91
90
91
91
91
90
Output: 220 / 230 / 240 Volts
Output: 200 / 208 / 250 Volts
11kVA /
8kWatts
90
89
91
90
90
90
90
89
Output: 220 / 230 / 240 Volts
Output: 200 / 208 / 250 Volts
Appendix
5 — 3
86-86000-00 B00