Dca-36spx — generator shut-down procedures – Multiquip MQ Power Whisperwatt Series DCA-36SPX User Manual
Page 38
PAGE 38 — DCA-36SPX— OPERATION AND PARTS MANUAL — REV. #1 (04/14/10)
Normal Shutdown Procedure
To shutdown the generator use the following procedure:
1. Place both the MAIN, GFCI and LOAD circuit breakers
as shown in Figure 39 to the OFF position.
2. Let the engine cool by running it at low speed for 3-5
minutes with no load applied.
3. Place the
MPEC Control Switch (Figure 42) to the
OFF/RESET position.
Figure 42. MPEC Control Switch (Off/Reset)
4. Verify that the
all status LED on the MPEC display
are OFF (not lit).
5. Remove all loads from the generator.
6. Inspect entire generator for any damage or loosening of
components that may have occured during operation.
Emergency Shutdown Procedure
1. Place the
MPEC Control Switch switch (Figure 42) to
the OFF/RESET position.
2. To shut-down the engine in the event of an emergency,
switch the
MAIN, GFCI and LOAD (Figure 39) circuit
breakers to OFF position.
DCA-36SPX — GENERATOR SHUT-DOWN PROCEDURES
NEVER stop the engine suddenly except in an emergency.
WARNING - SHUTTING DOWN THE GENERATOR